- 6 -

3.2 Siting of the Heat Pump

The appliance will operate properly in any location, provided that three

points are observed:

1. Fresh Air

-

2. Electricity

-

3. Swimming pool filters

The appliance may be installed practically anywhere

outside

, as long as

minimum distances to other objects are observed

.

3.3 Distance from the Swimming Pool

Install the heat pump as close as possible to the swimming pool in order to

limit heat loss through the pipes.

Ensure a firm base and place the heat pump on the rubber blocks to avoid

vibration. All exposed pipework is to

be insulated to avoid heat loss.

3.4 Installing the Check-Valve

N.B.

– When using automatic chlorine and pH dosing systems, it is

extremely important to protect the heat pump from excessive

concentrations that could damage the heat exchanger. For this

CAUTION:

Do not place the appliance in
an enclosed space with
restricted volume of air where
the air expelled would be
re-used, or near to shrubbery
that might block the air inlet.
These locations hinder the
continuous flow of fresh air,
resulting in a reduction in
efficiency and possibly
obstructing adequate supply
of heat.
See diagram for the

minimum

distances.

Содержание Green Energy ECO 10

Страница 1: ...58 Green Energy Heat pump 230V 5 horizontal 11059 Green Energy Heat pump 230V 8 horizontal 11060 Green Energy Heat pump 230V 10 horizontal 11061 Green Energy Heat pump 230V 12 horizontal Swimming Pool...

Страница 2: ......

Страница 3: ...uorinated greenhouse gases and handling safety the relevant type and size of equipment Record keeping 1 Operators of equipment which is required to be checked for leaks shall establish and maintain re...

Страница 4: ...n und der Handhabungssicherheit der betreffenden Typen und Gr e der Ausr stung beinhaltet Aufbewahrung der Aufzeichnungen 1 Die Betreiber von den Ger te die auf Dichtheit berpr ft werden m ssen m ssen...

Страница 5: ...ture when the air ambient temperature is at 7 to 40 ATTENTION This manual includes all necessary information for the usual practice of the Heat Pump please to read the Service Manual provide with this...

Страница 6: ...0 Running current A 3 4 4 9 7 4 8 10 6 Mininum fuse A 10 15 20 20 30 Maximum volume good insulation m 15 20 30 45 60 Nominal water flow m h 2 5 2 5 2 5 2 6 3 5 Maximum pressure drop kPa 12 12 12 12 15...

Страница 7: ...the water flow of the swimming pool pump is more than 20 above the permitted flow through the heat exchanger of the heat pump 3 Install the heat pump above the surface level of the swimming pool 4 Alw...

Страница 8: ...ump on the rubber blocks to avoid vibration All exposed pipework is to be insulated to avoid heat loss 3 4 Installing the Check Valve N B When using automatic chlorine and pH dosing systems it is extr...

Страница 9: ...heat pump and it is recommended to install a check valve to prevent reverse flow in the absence of water circulation Damage to the heat pump caused by failing to observe these precautions is not subje...

Страница 10: ...meantime to check the Inlet water temp Outlet water temp it will be optimum when the difference is around 2 degree Please take below steps to adjust the by pass 1 Valve 1 wide open Valve 2 valve 3 cl...

Страница 11: ...r this reason connect to the same fuse as the filter pump If no water flows through the heat pump while in operation it may be damaged and then the warranty is invalidated Connect the cable carrying t...

Страница 12: ...to bring the water up to the temperature required Covering the swimming pool properly can considerably shorten this period Time Delay the appliance is fitted with built in start up delay of 3 minutes...

Страница 13: ...ure and current working mode after 5s 3 Stop the pool heat pump Press once again to stop the heat pump the LED display shows OFF 4 Water temperature setting Press or to set the desired water in temper...

Страница 14: ...twice to enter into TIMER ON setting When you see the starting time displaying on controller Press to confirm to enter into TIMER ON setting interface finally press or to adjust the starting time 7 T...

Страница 15: ...as return temperature 29 to 99 F Ambient temperature 29 to 99 G Cooling pipe temperature 9 to 99 H Actual steps of Electronic expansion valve N 5 ATTENTION When you press and press button to enter int...

Страница 16: ...emp under cooling mode 7 35 C 28 C Not adjustable 1 To set the entering water temp under heating mode 15 42 C 28 C Adjustable 2 Entry into defrosting time period 30 90MIN 40MIN Adjustable 3 Terms of E...

Страница 17: ...long time specially during the winter season 4 In another way you should check the unit is water fully before the unit start to run again 5 After the unit is conditioned for the winter season he is pr...

Страница 18: ...ting condenser sensor failure PP3 The sensor in open or short circuit Check or change the sensor Gas return sensor failure PP4 The sensor in open or short circuit Check or change the sensor Ambient te...

Страница 19: ...e sensor Cooling outlet water temperature is too low PP7 Water flow volume is not enough Check the water flow or water system is jammed or not Cooling temperature is too cold PP9 The sensor in open or...

Страница 20: ...ation failure EE8 Wire connection is not good Check the wire connection 7 2 Other malfunction and solutions No display on controller Malfun ctions Observing Reasons Solution Heat pump is not runnin g...

Страница 21: ...temperature no error code displays 1 Fan NO running 2 Air ventilation is not enough 3 Refrigerant is not enough 1 Check the cable connections between the motor and fan if necessary it should be replac...

Страница 22: ...20 8 Electrical Wiring ECO 3 5 8 10 wiring diagram...

Страница 23: ...21 ECO 12 wiring diagram...

Страница 24: ...22 9 Figures of the pump 9 1 Exploded Diagram...

Страница 25: ...Piping 9 Left grill 33 Compressor 10 Motor fixture 34 Power cable connection 11 Base tray 35 Blue rubber ring 12 Motor 36 Gauge 13 Fan blade 37 Heat exchanger 14 Front panel 38 Water connection 15 Ve...

Страница 26: ...24 10 Accessories Anti vibration base 4 pcs Beneath the machine stand Draining jet 2 pcs Under the bottom panel...

Страница 27: ...25 11 Warranty and Returns 11 1 Warranty...

Страница 28: ...ity Zip Country Contact Phone E mail Fax Contact Date Internal use RMA Issued by Date Return for Copy of customer s invoice attached Other documents attached to RMA request Description of documents Mo...

Страница 29: ...umber will be allocated to you within 24 hours of receipt of the required documentation Absence of the information required in points 3 and 4 may result in refusal to allocate you an RMA number 6 The...

Страница 30: ...r aufheizen und auf einer konstanten Temperatur halten wenn die Au entemperatur zwischen 7 und 40 C liegt ACHTUNG Dieses Handbuch beinhaltet alle Informationen die f r die Benutzung und die Installati...

Страница 31: ...50 Laufender Strom A 3 4 4 9 7 4 8 10 6 Mininum Sicherung A 10 15 20 20 30 Maximales Volumen gute Isolierung m 15 20 30 45 60 Nennwasserdurchfluss m h 2 5 2 5 2 5 2 6 3 5 Maximaler Druckabfall kPa 12...

Страница 32: ...nn der Wasserfluss aus der Schwimmbadpumpe mehr als 20 gr er ist als der maximal zul ssige Durchfluss durch den W rmetauscher der W rmepumpe ist Installieren Sie die Wasserpumpe ber dem Wasserspiegel...

Страница 33: ...erlust durch die R hren zu minimieren Sorgen Sie f r einen festen Untergrund und plazieren Sie die W rmepumpe auf den Vibrationsd mpfern um berm ige Vibration zu vermeiden Alle R hren m ssen isoliert...

Страница 34: ...her korrodieren k nnten zu sch tzen Aus diesem Grund m ssen Ger te dieser Art stets in der Rohrleitung auf der stromabw rtigen Seite der W rmepumpe montiert werden und es wird empfohlen ein R ckschlag...

Страница 35: ...W rmepumpe zu Bitte f hren Sie die folgenden Schritte aus um den Bypass anzupassen 1 Ventil 1 weit ge ffnet Ventil 2 und Ventil 3 geschlossen 2 Ventil 2 und Ventil 3 halb ffnen danach Ventil 1 langsam...

Страница 36: ...ung der W rmepumpe bereinstimmt Es wird empfohlen die W rmepumpe an einen Stromkreis mit eigener Sicherung oder einem Schutzschalter langsamer Typ Kurve D und ausreichende Verkabelung anzuschlie en si...

Страница 37: ...emperatur kann es mehrere Tage dauern das Wasser auf die gew nschte Temperatur zu erw rmen Eine gute Schwimmbadabdeckung k nnte die erforderliche Zeit drastisch reduzieren Zeitverz gerung Die W rmepum...

Страница 38: ...einmal um die Lachew rmepumpe aufzuh ren Die LED Aneige zeigt OFF 4 Die Wassertemperatur einstellen D cken Sie oder um das gew nschte Wasser in der Temperatur im gegenw rtigen Arbeitsmodus ein Dann dr...

Страница 39: ...n dass die Anla zeit auf dem Kontroller angezeigt dann best tigen Sie bitte mit dass wir in die TIMER AUF Einstellungsschnittstelle treten Zuletzt stellen Sie die Anla zeit mit oder ein 7 TIMER AB ein...

Страница 40: ...ebende Temperatur 29 to 99 G Temperatur des Abk hlungsrohrs 9 to 99 H Tats chliche Schritte des elektronischen Expansion Ventils N 5 ACHTUNG Wenn Sie mit und in Parameter treten und berpr fen diese Ta...

Страница 41: ...ie Parameter Einstellung und zur ckgehen Param eter Bedeutung Umfang Standar d Anmerkung en 0 Die hereinkommende Wassertemperatur einstellen unter abk hlendem Modus 7 35 C 28 C Nicht verstellbar 1 Die...

Страница 42: ...d lange 10 10 Sekunden um die Werkseinstellungen wiederzuherstellen Das wird 0000 angezeigt und dann 6 Wartung 6 1 Wartung 1 Sie sollten das Wasserversorgungssystem regelm ig berpr fen um zu verhinder...

Страница 43: ...omatischer Chlorinator benutzt wird sollte er Stromabw rts von der W rmepumpe plaziert werden 6 2 K hlmitteldruck Um sicherzugehen dass die Einheit arbeitet berpr fen Sie den Druck am Manometer Die fo...

Страница 44: ...klauf PP4 Schlie en Sie einige Draht zu Unrecht in diesem Punkt Best tigen Sie gibt es nichts zu diesem Punkt Neustart Fehler beim Sensor f r die Umgebungstem peratur PP5 Drahtbruch oder Kurzschluss b...

Страница 45: ...lation is nicht genug 1 Entfernen Sie berfl ssige K hlmittel aus der HP Gasanlage 2 Reinigen Sie den Luft W rmetau sche Ausfall des Unterdruckschut z EE2 1 Zu wenig K hlmittel 2 Wasserflussme nge ist...

Страница 46: ...L sung werden nicht auf der LED Kabelsteuerung angezeigt Fehlfunk tion Anzeichen Ursachen L sung W rmep umpe l uft nicht LED Kabelsteuer ung hat keine Anzeige Keine Stromzufuhr berpr fen Sie ob Kabel...

Страница 47: ...ie lich berpr fen Sie die Wassereintritts und Austrittstemperatur 3 Ersetzen oder Reparieren Sie die Heipumpeneinheit Kurze Laufzeit en LED Bildschirm zeigt aktuelle Wassertemperat ur an kein Fehlerco...

Страница 48: ...n 2 berpr fen Sie den Luft W rmewechsle auf Defekte Zu viel Eis am Verdam pfer Zu viel Eis am Verdampfer 1 berpr fen Sie die Position der W rmepumpeneinh eit und entfernen Sie alle Hindernisse um eine...

Страница 49: ...47 8 Verkabelung ECO 3 5 8 10...

Страница 50: ...48 ECO 12...

Страница 51: ...49 9 Fakten zur Pumpe 9 1 Explodierte Zeichnung...

Страница 52: ...ker Grill 33 Kompressor 10 Motor Halterung 34 Energie Kabelverbindung 11 Niedriger Beh lter 35 Blauer Gummiring 12 Motor 36 Lehre 13 Ventilatorfl gel 37 W rmeaustauscher 14 Vorderseite 38 Wasser Verbi...

Страница 53: ...51 10 Zubeh r Anti Ersch tterung Unterseite 4 St ck Unter dem Maschine Standplatz Trockenlegung des Strahles 2 St ck Unter der unteren Verkleidung...

Страница 54: ...Teile oder Zubeh rteile in Zusammenhang mit dem Produkt 8 Chemische Verschmutzung der Verbrennungsluft oder unsachgem e Verwendung von Desinfektionschemikalien wie die Einleitung von Desinfektionschem...

Страница 55: ...Ansprech partner Datum Interne Verwendung RMA Nummer Ausgestellt von Datum R cksendung wegen Kopie der Kundenrechnung beigelegt Andere Unterlagen dem RMA Antrag beigelegt Beschreibung der Unterlagen...

Страница 56: ...Mail Eine RMA Nummer wird binnen 24 Stunden nach Erhalt der ordnungsgem en Dokumente ausgestellt Wenn die in Punkt 3 und 4 angegebenen Informationen fehlen kann die Ausstellung einer RMA Nummer verwe...

Страница 57: ......

Страница 58: ...A0111KWDE01...

Отзывы: