- 1 -
Regulation (EU) n° 517/2014 of 16/04/14 on fluorinated
greenhouse gases and repealing Regulation (EC) n° 842/2006
Leak checks
1.
Operators of equipment that contains fluorinated greenhouses gases in
quantities of 5 tons of CO
2
, equivalent
or more and not contained in foams shall
ensure that the equipment is checked for leaks.
2. F
or equipment that contains fluorinated greenhouse gases in quantities of 5
tons of
CO
2
equivalent or more, but of less than 50 tons of
CO
2
equivalent: at
least every 12 months.
Picture of the equivalence CO
2
1.
Load in kg and Tons amounting CO
2
.
Load and Tons amounting CO
2
Frequency of test
From 2 at 30 kg load = from 5 at 50 Tons
Each year
Concerning the Gaz R 410a, 2.39kg amounting at 5 tons of CO
2
, commitment
to check each year.
Training and certification
1.
The operator of the relevant application shall ensure that the relevant
personnel have obtained the necessary certification, which implies appropriate
knowledge of the applicable regulations and standards as well as the necessary
competence in emission prevention and recovery of fluorinated greenhouse
gases and handling safety the relevant type and size of equipment.
Record keeping
1.
Operators of equipment which is required to be checked for leaks, shall
establish and maintain records for each piece of such equipment specifying the
following information:
a) T
he quantity and type of fluorinated greenhouse gases installed
;
b)
The quantities of fluorinated greenhouse gases added during installation,
maintenance or servicing or due to leakage;
c) W
hether the quantities of installed fluorinated greenhouse gases have been
recycled or reclaimed, including the name and address of the recycling or
reclamation facility and, where applicable, the certificate number;
d)
The quantity of fluorinated greenhouse gases recovered
e) T
he identity of the undertaking which installed, serviced, maintained and
where applicable repaired or decommissioned the equipment, including, where
applicable, the number of its certificate;
f) T
he dates and results of the checks carried out;
g) I
f the equipment was decommissioned, the measures taken to recover and
dispose of the fluorinated greenhouse gases.
2. The operator shall keep the records for at least five years, undertakings carrying
out the activities for operators shall keep copies of the records for at least five
years.
Содержание Green Energy ECO 10
Страница 2: ......
Страница 22: ...20 8 Electrical Wiring ECO 3 5 8 10 wiring diagram...
Страница 23: ...21 ECO 12 wiring diagram...
Страница 24: ...22 9 Figures of the pump 9 1 Exploded Diagram...
Страница 26: ...24 10 Accessories Anti vibration base 4 pcs Beneath the machine stand Draining jet 2 pcs Under the bottom panel...
Страница 27: ...25 11 Warranty and Returns 11 1 Warranty...
Страница 49: ...47 8 Verkabelung ECO 3 5 8 10...
Страница 50: ...48 ECO 12...
Страница 51: ...49 9 Fakten zur Pumpe 9 1 Explodierte Zeichnung...
Страница 57: ......
Страница 58: ...A0111KWDE01...