E-6
English
8
8 Faults / Troubleshooting
Each message appears in plain text on the display.
ATTENTION!
Any work on the device may only be performed by authorised and
qualified after-sales service technicians.
8.1 Fault calculation table
8.2 Basic settings
9 Decommissioning /
Disposal
Shut off the voltage before dismantling the device. Observe all
environmentally-relevant requirements regarding the recovery,
recycling and disposal of materials and components in accor-
dance with all applicable standards. Particular attention should
be paid to the proper disposal of refrigerants.
Complaint
Possible fault(s)
Possible cause(s)/correction
Device does not run
Infeed interrupted
Safety measures, protective motor switch or fault current protective switch have been acti-
vated / switch on again
Control fuse in the device has tripped
Wiring error – failure due to surge or short circuit / switch on circuit breaker; replace fuse
Fault in refrigerant circuit
Device component defective / Notify KVS customer service
Fault messages display
Operating limit
Operation outside of the operating limits
Temperature too low / high / adjust ambient conditions to specified values
Low pressure switch
Expansion valve; leakage
Cut-off due to low pressure
Notify KVS customer Service
Lack of heat in refrigerant circuit / notify KVS customer service
High-pressure switch
Cut-off due to high pressure
Excess heat in refrigerant circuit / notify KVS customer service
Idle time
Last activation or deactivation took place a
short while ago.
Wait for delay time (approx. 5 minutes)
Sensor fault
Sensor defective and/or not connected
Inform the KVS after-sales service
Target values
30 °C / 60%
Permissible room temperature
+15 to +38 °C, at least 2 K above pool water temperature
Safety switch setting
High pressure
Low-pressure
Off 25 bar
Off 2.2 bar
On 4.2 bar
Over-heating and supercooling
Approx. 2 to 8 K