R60047.0002 - Index 2
EN – page 89 / 115
13
Response times
13.1
Response Time of the Relay Output
Hardware delay of the relay itself:
25 ms (max.)
With normal monitoring of overspeed, underspeed or frequency band:
(with frequency band please choose the lower frequency, since this produces more delay)
2 x Sampling Time + 25 ms
e.g. f = 10 kHz, Sampling Time = 1 ms
for frequencies > 1 / Sampling Time
10 kHz > 1 kHz -> delay = 27 ms
2 x 1/fre 25 ms
e.g. f = 100 Hz, Sampling Time = 1 ms
for frequencies < 1 / Sampling Time
100 Hz < 1 kHz -> delay = 45 ms
With normal monitoring of standstill:
2 x Wait Time + Standstill Time + 25 ms
e. g. Standstill Time = 0 ms, Wait Time = 100
ms
for frequency = 0
delay = 225 ms
These response times are based on a step function.
For this time, the parameter “Filter” is not regarded. If Filter is activated,
Sampling Time or 1/frequency has to be multiplied by the factor x 5. (5 = a final
value about 100% is reached, 3= a final value about 95% is reached).
With a system error (critical internal error) the response time will be:
85 ms + 25 ms =110 ms.
13.2
Response Time of the Analog Output
Hardware delay of the analog output itself:
1 ms
With normal monitoring of overspeed, underspeed or frequency band:
(with frequency band please choose the lower frequency, since this produces more delay)
2 x Sampling Time + 1 ms
e.g. f = 10 kHz, Sampling Time = 1 ms
for frequencies > 1 / Sampling Time
10 kHz > 1 kHz -> delay = 3 ms
2 x 1/fre 1 ms
e.g. f = 100 Hz, Sampling Time = 1 ms
for frequencies < 1 / Sampling Time
100Hz < 1 kHz -> delay = 21 ms
With normal monitoring of standstill:
2 x Wait Time + Standstill Time + 1 ms
e.g. Standstill Time = 0, Wait Time = 100 m s
for frequency = 0
delay = 201 ms
These response times are based on a step function.
For this time, the parameter “Filter” is not regarded. If Filter is activated,
Sampling Time or 1/frequency has to be multiplied by the factor x 5. (5 = a final
value about 100% is reached, 3= a final value about 95% is reached).
With a system error (critical internal error) the response time will be:
85 ms + 1 ms =86 ms
Содержание SMC1.3
Страница 44: ...R60047 0001 Index 2 DE Seite 44 120 8 2 Montage Demontage...
Страница 49: ...R60047 0001 Index 2 DE Seite 49 120...
Страница 117: ...R60047 0001 Index 2 DE Seite 117 120 20 Zertifikat...
Страница 118: ...R60047 0001 Index 2 DE Seite 118 120...
Страница 119: ...R60047 0001 Index 2 DE Seite 119 120...
Страница 131: ...R60047 0002 Index 2 EN page 11 115 4 3 SMC1 3 Block Diagram 4 4 SMC1 3 Connections The figure shows the available ports...
Страница 163: ...R60047 0002 Index 2 EN page 43 115 8 2 Mounting Dismounting...
Страница 168: ...R60047 0002 Index 2 EN page 48 115...
Страница 233: ...R60047 0002 Index 2 EN page 113 115 19 1 Dimensions incl SMCB on front Front Rear SMC2 4 SMCB option...
Страница 234: ...R60047 0002 Index 2 EN page 114 115 20 Certificate...