R60047.0002 - Index 2
EN – page 85 / 115
12.22 No Standstill (Switch Mode = 20)
If the parameter „Switch Mode“ is set to 20, the functionality corresponds to the inverted
Switch Mode = 3. The function is always active as in the Switch Mode = 3, but the output
can only be set up statically.
With this function, the relay output is invertedly controlled to the Switch Mode=3, the
relay is closed at standstill and opened for frequencies different to zero. The Standstill
Time defines a delay before standstill is detected.
Relevant Parameters
Remark
Switch Mode XXXX
= 20
Pulse Time XXXX
Only statically = 0
Standstill Time
Standstill time in x seconds
Output Mode
homogenous or inverse output configuration (affects the Safety
Integrity Level SIL)
Relevant Input function
Remark
no
no
12.23 Ramp monitoring (Switch Mode = 21)
With parameter setting “Switch Mode” = 21, a ramp monitoring function is assigned to
the output. The requirement for ramp monitoring is that the braking behavior follows a
linear function of frequency and time. During the transition from inactive to active
enable flank, the current frequency is cached in the device and the expected frequency
can be determined by the pre-programmed ramp parameter "Presel.
.F". If the
current frequency deviates so that the precalculated window "Presel.
.
" is left,
the output is set. An enable input signal is required for the function, which is assigned by
the parameter "Matrix
". A lock function can be attributed. The lock function can
be acknowledged by a further input. A confirmation is only possible if the enable signal is
disabled.
Relevant Parameters
Remark
„Switch Mode
“
= 21
„Matrix
“
use only inputs, but no feedback outputs
„MIA-Delay
“
= 0 (can also be set according to need)
„MAI-Delay
“
= 0 (can also be set according to need)
„Lock Output“
for lock function use only range 0-31
„Output Mode“
homogenous or inverse output configuration (affects the Safety Integrity
Level SIL/PL)
„Delay
“
„Presel.
.
“
+/-range from the cached center point
„Presel.
.F“
Entering the brake ramp
„Input Mode “
configuration of the control inputs (affects the safety level SIL/PL)
„ IN Function“
function of the control input
Содержание SMC1.3
Страница 44: ...R60047 0001 Index 2 DE Seite 44 120 8 2 Montage Demontage...
Страница 49: ...R60047 0001 Index 2 DE Seite 49 120...
Страница 117: ...R60047 0001 Index 2 DE Seite 117 120 20 Zertifikat...
Страница 118: ...R60047 0001 Index 2 DE Seite 118 120...
Страница 119: ...R60047 0001 Index 2 DE Seite 119 120...
Страница 131: ...R60047 0002 Index 2 EN page 11 115 4 3 SMC1 3 Block Diagram 4 4 SMC1 3 Connections The figure shows the available ports...
Страница 163: ...R60047 0002 Index 2 EN page 43 115 8 2 Mounting Dismounting...
Страница 168: ...R60047 0002 Index 2 EN page 48 115...
Страница 233: ...R60047 0002 Index 2 EN page 113 115 19 1 Dimensions incl SMCB on front Front Rear SMC2 4 SMCB option...
Страница 234: ...R60047 0002 Index 2 EN page 114 115 20 Certificate...