EN 22/38
Manual
Limes LA50 / BA5
Absolute Magnetic Length Measurement System
7.3 Interface CANopen
The measuring system with a CAN interface is equipped in compliance with CANopen
Standard DS406. A NMT command is issued to start the communication.
The following identifiers are given:
CAN - Identifier
(6 Byte telegram)
181 (16) = Identifier
First 4 bytes = Position (Resolution 0.01 mm), Baud rate 250 KB/s
Following 2 bytes = speed in mm/s
The CAN-Identifier can be adjusted in the range of 181
(16)
to 18F
(16)
by a decoding switch,
which is located behind a protection cap on the top of the sensor housing:
Position 0 of the address coding switch fetches the address from the memory. If no address is
saved in the memory, the default setting 181h is used.
Position 8 of the bit rate coding switch fetches the bit rate stored in the EEPROM If no bit rate
has been saved, it will be set to 1 Mbit/s.
Position
CAN Identifier
Position
CAN Identifier
Position
Baud rate
0
Identifier from memory
8
188
8
Baud rate from memory
1
181
9
189
9
1M
2
182
A
18A
A
800k
3
183
B
18B
B
500k
4
184
C
18C
C
250k*
5
185
D
18D
D
125k
6
186
E
18E
E
100k
7
187
F
18F
F
50k
*default
Position
LSB
MSB
LSB
MSB
Byte:
0
1
2
3
4
5
Speed
LED
Baud rate
Address
Terminating
impedance