7 Operation
32 of 52
Calio S
1157.8117/01-EN
Symbol
Description
Unit
Open-loop Control operating mode
▪
Symbol lights up when this operating mode is active.
▪
The bar diagram shows the active speed level.
-
Setback Operation function
▪
Symbol lights up when this operating mode is active.
-
Service mode (only for KSB Service)
▪
Symbol lights up when this function is active.
▪
Control panel remains operational when drive is stopped.
-
Fault message (e.g. error code E8)
▪
An error code (E01 - E09) is shown on the display.
-
7.2 Operating modes
7.2.1 Information on settings
For common applications such as two-pipe systems Proportional-pressure Control (Δp-
v) is the recommended operating mode. This operating mode offers an extended
control range with additional potential savings compared to Constant-pressure
Control (Δp-c). Depending on the balancing of branch circuits, undersupply may
occur at a consumer installation.
Constant-pressure Control operating mode (Δp‐c) can optionally be selected for
underfloor heating systems, for example. If noises are audible at low flow rates,
select the Proportional-pressure Control operating mode (Δp-v).
The setting of the discharge head setpoint depends on the piping curve of the system
and on the heat requirements. As standard the pump set is pre-set to Proportional-
pressure Control (Δp-v) operating mode.
Table 13:
Standard setting of discharge head setpoint
Size
Discharge head setpoint
[m]
15-40-130
2
15-60-130
3
25-40-130
2
25-60-130
3
25-40
2
25-60
3
25-80
4
30-40
2
30-60
3
30-80
4