5 Installation at Site
19 of 52
Calio S
1157.8117/01-EN
5.3 Installing the pump set
DANGER
Leakage at the pump
Leakage of hot fluids!
▷
Fit the sealing elements and make sure they are positioned correctly.
CAUTION
Fluid entering the electronic system housing
Damage to the pump set!
▷
Install the pump set with the pump shaft in horizontal position. Connect the
piping without transmitting any stresses and strains.
▷
Never install the pump set with the electronic system housing pointing upwards
or downwards.
▷
Undo the hexagon socket head cap screws. Then turn the electronic system
housing.
CAUTION
Air entering the pump
Damage to vertically installed pump sets whose direction of flow is downwards!
▷
Fit a vent valve at the highest point of the suction line.
NOTE
Installing shut-off valves upstream and downstream of the pump set is
recommended. Make sure that no leakage drips onto the pump set.
NOTE
The direction of flow of a vertically installed pump should be upwards.
NOTE
Do not install the pump at the lowest point of the system to prevent any impurities
from collecting in the pump.
The control panel can be turned. The position must be effected with the pump set
removed from the system.
1. Undo and store the 4 hexagon socket head cap screws.
2. Rotate the drive unit until it has reached the required position. Compare it
against the permissible installation positions. Adjust the position if required.
3. Fit and tighten the 4 hexagon socket head cap screws again.