8 Servicing/Maintenance
44 of 52
Calio S
1157.8117/01-EN
WARNING
Strong magnetic field
Danger of crushing injuries when pulling out the pump rotor!
Strong magnetic field can suddenly pull the pump rotor back into its original
position!
Danger of magnetic parts near the pump rotor being attracted!
▷
The pump rotor must be removed from the electronic system housing by
authorised specialist personnel only.
▷
Remove any magnetic parts from the vicinity of the rotor.
▷
Keep the assembly area clean.
▷
Keep a safety distance of at least 0.3 m from electronic components.
WARNING
Hot surface
Risk of injury!
▷
Allow the pump set to cool down to ambient temperature.
CAUTION
Strong magnetic field in the pump rotor area
Interference with magnetic data carriers, electronic devices, components and
instruments!
Uncontrolled magnetic attraction forces between magnetic components, tools or
similar!
▷
The rotor must generally be removed from the electronic system housing by
authorised specialist personnel only.
▷
Remove any magnetic parts from the vicinity of the pump rotor.
▷
Keep the assembly area clean.
ü
The pump set has been de-energised and secured against unintentional start-up.
ü
The pump has cooled down to ambient temperature.
ü
A container for collecting the fluid has been positioned underneath the pump
set.
1. Close the shut-off elements.
2. Disconnect the discharge nozzle and suction nozzle from the piping.
3. Depending on the pump size / motor size, remove the supports from the pump
set.
4. Remove the complete pump set from the piping.