ID.: 17-16-24-3004-02 | 6.2017
19
CAUTION
For normal operation of the expansion tank, it is necessary to perform proper
adjustments of the tank’s working pressure. The pressure is adjusted according to
the pressure of the water supply. The settings have to be checked every 6 months.
5.4 Installation of air ducts.
The device has connections for air ducts installed on the casing. The diameter of the
connection hole is
φ
180 mm which enables the connection of standard air ducts
φ
150 mm
(internal diameter) from our sales catalogue (hoses Isopipe or Centrotherm); you can also use
sewage pipes with the diameter of
φ
160 mm (internal diameter). In case of using pipes without
insulation, the pipes have to be insulated to prevent water condensation on the surface of the
pipe.
The construction of the casing enables turning the air connections upwards and sideways
enabling changing the direction of air intake and outlet. This way the device can be optimally
placed into the room (minimal clearance from the walls), the number of elements and air ducts
which cause additional air pressure drops and lessen the characteristics of the device can be
reduced.
To change the direction of air duct connections, it is necessary to remove the screws on the
cover of the device and remove the cover
Picture 8). After removing the cover, the air ducts can be pulled out upwards and turned with
the opening facing upwards or sideways.
Picture 8: Changing the direction of air duct connections
The openings of the air duct connections are turned to the side by default. In case of a
malfunction near the air connection it is recommended to turn the connection and thus enable
easier air flow through the device.
1
2
3
2
3
Imbus 4
Screwing torque max. 0,5 Nm