Rev. Date: 3/14/18
Page 11
MODEL #500
input cord on unit and not to exceed 50' in length.
(See Voltage Drop Chart Below.) Caution:
Operating unit with less than required voltage or inadequate generator size will result in damage to
electrical components. This machine is marked with the correct input voltage on input cords located
on bottom of the Main Control Panel.
Note:
Agitator motor and blower(s) should only be operated
with steady or constant flow of electricity.
Do not
operate machine with less than required voltage.
Damage to motors and other electrical parts will result. Check voltmeter on Main Control Panel when
machine is running.
Ex: A two-wire 20-ampere circuit using 12 AWG with a one-way distance of 25 feet will drop 1.98 volts;
120 volts - 1.98 volts = 118.02 volts as the load voltage.
230 volts - 1.98 volts = 228.02 volts as the load voltage.
240 volts - 1.98 volts = 238.02 volts as the load voltage.
2.
For 240volt, 60hz. models only,
properly connect female receptacle to extension cord. See
illustration F and consult electrician for assistance.
Содержание 500
Страница 37: ...Rev Date 3 14 18 Page34 MODEL 500 NON SHREDDER UPPER HOPPER and LOWER BASE UNIT ASSEMBLY ...
Страница 40: ...Rev Date 3 14 18 Page37 MODEL 500 SHREDDER UPPER HOPPER and LOWER BASE UNIT ASSEMBLY ...
Страница 43: ...Rev Date 3 14 18 Page40 MODEL 500 BLOWER BOX ASSEMBLY ...
Страница 45: ...Rev Date 3 14 18 Page42 MODEL 500 MECHANICAL and ELECTRICAL CONTROL ASSEMBLY OPTIONS ...
Страница 47: ...Rev Date 3 14 18 Page44 MODEL 500 OPTIONALSHREDDERASSEMBLY HOPPEREXTENSION ...
Страница 58: ...Rev Date 3 14 18 Page55 MODEL 500 SERVICE RECORD DATE MAINTENANCE PERFORMED COMPONENTS REQUIRED ...