Outdoor Covered Fireplace Installation
SECTION 3
FRAMING
#SP-41-L
R.6 February 2022
17
HUSSONG MFG. CO., INC.
KOZY HEAT FIREPLACES
3.7 Outdoor Covered Fireplace Installation
A outdoor covered fireplace installation allows a fireplace to be
installed in an outdoor covered area, where the appliance is protected
from direct precipitation.
Follow the instructions and illustrations in this section for installation
procedures.
3.7.1 Safety Screen Barriers
Hussong Mfg. highly recommends to use black painted safety barriers
in outdoor installations. Other screen barriers that incorporate
a plated or patina finish are highly susceptible to oxidation and
discoloration.
3.7.2 Requirements
•
The continuous insulated building envelope and weatherproof
membrane are not to be interrupted by fireplace installation. See
on the following page.
•
Fireplace operation is approved from 40°F to 110°F.
•
All wiring connections shall be in accordance with outdoor
requirements of NECA NFPA 70.
•
All clearances and requirements in your appliance manual must
be adhered to.
A
B
C
C
The overhang (A) must be a minimum of 1/2 or
greater of the roofline elevation (B) above the base
of the fireplace.
The width of the overhang to each side of the
appliance (C) must be a minimum of 1/2 or
greater of the roofline elevation (B) above the
base of the fireplace.
EXAMPLE: If roofline (B) is 10’ above the base of fireplace, the overhang (A) must be 5’
or greater. The width of the overhang to EACH side of the fireplace (C) must be 5’ or greater.
SIDE OF
FIREPLACE
BACK OF
FIREPLACE
FRONT OF
FIREPLACE
ROOF OVERHANG
FIGURE 3.6
Outdoor Covered Fireplace Install - 1