HORIZONTAL / VERTICAL COMBINATION:
(4.57m) 15' Vertical
(3.05m) 10' Horizontal
Termination must be
within shaded area
(ft.) 0
2
4
6
8
10
12
14
16
20
22
18
24
26
28
30
40
38
36
34
32
10 12 14 16 18 20 22 24 26 28 30
(6.1m)
(6.1m)
(12.9m)
(9.14
m)
0 2 4 6 8
VENTING
(Horizontal & Vertical Combination)
CAUTION: This gas appliance
must not be connected to or
joined with any other chimney
flue serving another appliance.
PAGE 26
NOTE: Page 25 has information on restrictor installation in conjunction with venting installation.
Page 50 has information on restrictor recommendations depending on burner flame appearance and instructions on installation after
venting is completed.
Horizontal sections require 1/4” (6 mm) rise for every 12” (305 mm) of travel.
For each additional elbow used after the first elbow, 3 ft. (914 mm) must be subtracted from the maximum venting allowed. For each 45° elbow used, 1-1/2 ft.
(457 mm) must be subtracted from the maximum venting allowed.
(2) 45° degree elbows may be used in place of (1) 90° elbow.
IMPORTANT: THE HORIZONTAL VENT HEAT SHIELD MUST BE INSTALLED WHEN USING A 45-DEGREE ELBOW DIRECTLY
OFF FIREPLACE TO HORIZONTALLY POSITION THE VENT SYSTEM. EXCEPTION: CORNER INSTALLATIONS
THE KOZY HEAT WALL PASS-THRU, PART #800-WPT (4-1/2” (114 mm) - 6-1/2” (165 mm) WALL THICKNESS) OR #800-WPT2 (6-1/2” (165
mm) - 12-1/2” (318 mm) WALL THICKNESS), MUST BE USED ON ALL HORIZONTAL VENT RUNS.