VENTING
(Horizontal)
NOTE: Horizontal sections re-
quire 1/4” (6 mm) rise for every
12” (305 mm) of travel.
HORIZONTAL TERMINATIONS
MAXIMUM HORIZONTAL VENTING: OPTION #1
CAUTION: This gas appliance must
not be connected to or joined with
any other chimney flue serving
another appliance.
PAGE 22
5 ft.
(1.52 m)
TERMINATION CAP
45° ELBOW
NOTE: Page 25 has information on restrictor installation in conjunction with venting installation. Page 50 has information on restrictor
recommendations depending on burner flame appearance and instructions on installation after venting is completed.
TERMINATION CAP
MINIMUM HORIZONTAL VENTING
6” (152 mm) VENT
PIPE SECTION
45° ELBOW
HORIZONTAL VENT
HEAT SHIELD
IMPORTANT: THE HORIZONTAL VENT HEAT SHIELD MUST BE INSTALLED WHEN USING A 45-DEGREE ELBOW DIRECTLY
OFF FIREPLACE TO HORIZONTALLY POSITION THE VENT SYSTEM. EXCEPTION: CORNER INSTALLATIONS
THE KOZY HEAT WALL PASS-THRU, PART #800-WPT (4-1/2” (114 mm) - 6-1/2” (165 mm) WALL THICKNESS) OR #800-WPT2 (6-1/2” (165
mm) - 12-1/2” (318 mm) WALL THICKNESS), MUST BE USED ON ALL HORIZONTAL VENT RUNS.
MAXIMUM HORIZONTAL VENTING: OPTION #2
10 ft.
(3.05 m)
TERMINATION CAP
45° ELBOW
6” (152 mm) VENT
PIPE SECTION
Horizontal vent heat shield not shown for clarity purposes only.