For each additional 90° elbow used after the first elbow, 3 ft. (914 mm) must be subtracted from the maximum allowed venting. For
each 45° elbow used, 1-1/2 ft. (457 mm) must be subtracted from the maximum venting allowed.
IMPORTANT: Consult the local and national installation codes
to assure adequate combustion and ventilation air is available.
IMPORTANT: Flame height and appearance will vary depending upon
venting configuration and type of fuel used. Venting requirements apply
to both Natural and LP gas.
VENTING
PAGE 20
APPROVED VENTING
NOTE: (2) 45° degree elbows may be used in place of (1) 90° elbow.
HORIZONTAL TERMINATIONS
MINIMUM: 45° elbow + 6” (152 mm) hori termination cap.
MAXIMUM:
OPTION #1: 45° elbow + 5 ft. (1.52 mm) + termination cap.
OPTION #2: 6” + 45
˚
elbow + 10 ft. (3.05 m) + termination cap.
ELBOWS
A restrictor is included in fireplace components packet.
Each installation is unique and affected by various factors including venting configuration, altitude and climate. Therefore, after
fireplace installation is complete a restrictor may be required or may need to be removed or modified.
Please refer to page 25
for installation instructions if installing the restrictor in conjunction with the venting.
Page 50 has information on restrictor recommendations depending on burner flame appearance and instructions on installation after
venting is completed.
RESTRICTOR
IMPORTANT: THE HORIZONTAL VENT HEAT SHIELD MUST BE INSTALLED WHEN USING A 45-DEGREE ELBOW DIRECTLY
OFF FIREPLACE TO HORIZONTALLY POSITION THE VENT SYSTEM. EXCEPTION: CORNER INSTALLATIONS
THE KOZY HEAT WALL PASS-THRU, PART #800-WPT (4-1/2” (114 mm) - 6-1/2” (165 mm) ) WALL THICKNESS OR #800-WPT2 (6-1/2” (165
mm) - 12-1/2” (318 mm) ), MUST BE USED ON ALL HORIZONTAL VENT RUNS.
Refer to the vent systems manufacturer's installation manual for complete installation instructions.
Installation must conform with the venting requirements and restrictions as outlined in this manual.
Simpson Dura-Vent DV-GS 5” x 8” direct vent system (horizontal and vertical terminations).
Ameri-Vent Direct Chimney System 5” x 8” (horizontal and vertical terminations).
Metal Fab Direct Chimney System 5” x 8” (horizontal and vertical terminations).
ICC Direct Chimney Systems 5” x 8” (horizontal and vertical terminations).
Selkirk-Metalbestos Chimney Systems 5” x 8” (horizontal and vertical terminations).
Kozy Heat #800 series flexible vent system (horizontal terminations).
HORIZONTAL VENT SYSTEM CLEARANCES
TOP
BOTTOM
SIDES
ALL APPROVED VENTING
3 inches (76 mm)
1 inch (25 mm)
1 inch (25 mm)