DIRECT VENT FIREPLACE 

WARNING

:  This product must be installed by 

a licensed plumber or gas fitter when installed 

in the Commonwealth of Massachusetts. 

 
IMPORTANT: Installation of a CO detector is 

required in the fireplace room when installed in 

the Commonwealth of Massachusetts. 

 

  

Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or          

 

    any other appliance. 

 

 IF YOU SMELL GAS: 

 

  Do not light any appliance. 

 

  Do not touch any electrical switch: do not use any phone in your building. 

 

  Immediately call gas supplier from a neighbors phone.  Follow the gas supplier instructions. 

 

  If you cannot reach your gas supplier, call the fire department. 

      

  Installation and service must be performed by a qualified installer, service agency or the gas 

           

 

     

supplier.

 

WARNING:  

If the information in these instructions are not followed exactly, a fire or  

explosion  may result, causing property damage, personal injury or loss of life. 

This appliance may be installed in an aftermarket permanently located, manufactured (mobile) home, 
where not prohibited by local codes. 

This appliance is only for use with the type (s) of gas indicated on 
the rating plate. A conversion kit is supplied with the appliance. 

www.kozyheat.com 

INSTALLATION  

AND  

OPERATION MANUAL 

Quality Fireplaces for Life 

DO 

NO

T  

DISC

ARD

 

INSTALLER: LEAVE THIS MANUAL WITH THE APPLIANCE. 
 
CONSUMER: RETAIN THIS MANUAL FOR FUTURE REFERENCE.

 

April 2009 

PRC-04-09-R06 

Содержание PRINCETON RPC-36

Страница 1: ...ou cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier WARNING If the information in these in...

Страница 2: ...ourselves in being dedicated to not only function and reliability but customer safety as well We offer our continual support and guidance to help you achieve the maximum benefit and enjoyment from you...

Страница 3: ...T Wall Pass Thru Installation Instructions 21 VENTING cont Horizontal Min Max Venting Illustrations 22 23 Vertical Vent System Clearances 24 Vertical Termination Minimum Maximum 24 Combustion Air Inta...

Страница 4: ...appliance should be located out of traffic and away from furniture and draperies The glass front or any part removed for servicing the appliance must be replaced prior to operating the appliance Work...

Страница 5: ...hermostat remote control Wall mount thermostat wireless wall mount thermostat Decorative full door faces in various styles and finishes Renaissance pattern front Mission design doors in various finish...

Страница 6: ...eet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print no less the one half inch 1 2 in size...

Страница 7: ...DE THE 10 254 mm MINIMUM CLEARANCE TO HEADER USE ONLY NON COMBUSTIBLE MATERIAL IN THIS AREA FOR THE ENTIRE WIDTH OF FIREPLACE DO NOT USE WOOD SHEET ROCK ETC IN THIS ZONE NOTE OTHER CLEARANCES APPLY AL...

Страница 8: ...USE ONLY NON COMBUSTIBLE MATERIAL IN THIS AREA FOR THE ENTIRE WIDTH OF FIREPLACE DO NOT USE WOOD SHEET ROCK ETC IN THIS ZONE NOTE OTHER CLEARANCES APPLY ALL CLEARANCES MUST BE MAIN TAINED REFER TO PA...

Страница 9: ...ttach nailing flanges to fireplace 4 Insert fireplace into framing 5 Install the hearth if applicable 6 Complete the gas line installation 7 Complete the electrical hook up Install any standard or opt...

Страница 10: ...T THE TOP STAND OFF BRACKETS MUST BE FORMED AND AT TACHED PRIOR TO POSITIONING THE FIREPLACE INTO FRAMED OPENING WARNING NON COMBUSTIBLE ZONE STAND OFFS PROVIDE THE 10 254 mm MINI MUM CLEARANCE TO HEA...

Страница 11: ...MUST BE INSTALLED WHEN USING A 45 DEGREE ELBOW TO HORIZONTALLY POSITION THE VENT SYSTEM EXCEPTION CORNER INSTALLATIONS To Install Horizontal Vent Heat Shield Attach here Tighten screws NAILING FLANGE...

Страница 12: ...rative doors full door faces access the control valve installation of gas line fan etc PAGE 11 WARNING DO NOT OBSTRUCT UPPER AND LOWER GRILL OPENINGS ROOM AIR ENTERS THROUGH THE LOWER PAS SAGE IS HEAT...

Страница 13: ...Minimum plat form size 35 7 8 911 mm wide x 21 3 8 543mm deep FIRE HAZARD Do NOT install directly on carpeting vinyl or any combustible material other than wood IMPORTANT Vent cap location must be in...

Страница 14: ...THE TOP OF UNIT TO HORIZONTALLY POSITION THE VENT SYSTEM EXCEPTION CORNER INSTALLATIONS TYPICAL INSTALLATION OPTIONS TYPICAL CORNER INSTALLATION TYPICAL VERTICAL INSTALLATION TYPICAL HORIZONTAL INSTA...

Страница 15: ...MANTEL REQUIREMENTS PAGE 14 WARNING TOP STAND OFF BRACKETS MUST BE ASSEMBLED AND ATTACHED TO FIREPLACE DO NOT REMOVE CAUTION STAND OFF BRACKETS ARE NOT LOAD BEARING...

Страница 16: ...front B Pull top handles out and down to secure glass frame assembly top C Pull bottom handles out and up to secure glass frame assembly bottom CAUTION TO PREVENT GLASS FRAME ASSEMBLY FROM FALLING OFF...

Страница 17: ...Refer local electrical codes for specific requirements WARNING THIS APPLIANCE IS EQUIPPED WITH A THREE PRONG GROUNDING PLUG FOR PROTECTION AGAINST SHOCK HAZARD AND SHOULD BE PLUGGED DIRECTLY INTO A PR...

Страница 18: ...od Refer to page 36 of this installation manual if necessary Before adjusting the temperature control switch unplug the 3 prong plug on the fan cord from the receptacle Adjust position of the temperat...

Страница 19: ...liance and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that system at pressures in excess of psi NOTE The appliance must be isola...

Страница 20: ...rol IMPORTANT The insulated cover included with the remote control must be placed over the remote receiver to prevent overheating IMPORTANT If ON OFF rocker switch wires are not disconnected the ON OF...

Страница 21: ...ling the restrictor in conjunction with the venting Page 50 has information on restrictor recommendations depending on burner flame appearance and instructions on installation after venting is complet...

Страница 22: ...pass thru section marked 1 with 3 8 10 mm flange into framed opening Secure to interior wall with screws not pro vided C From the exterior place insulation between flange and top of framed opening in...

Страница 23: ...rance and instructions on installation after venting is completed TERMINATION CAP MINIMUM HORIZONTAL VENTING 6 152 mm VENT PIPE SECTION 45 ELBOW HORIZONTAL VENT HEAT SHIELD IMPORTANT THE HORIZONTAL VE...

Страница 24: ...OTE Page 25 has information on restrictor installation in conjunction with venting installation Page 50 has information on restrictor recommendations depending on burner flame appearance and instructi...

Страница 25: ...structions on installation after venting is completed RESTRICTOR VERTICAL VENT SYSTEM CLEARANCES TOP BOTTOM SIDES ALL APPROVED RIGID PIPE 1 inch 25 mm 1 inch 25 mm 1 inch 25 mm KOZY HEAT 800 SERIES DO...

Страница 26: ...ecommendations depending on burner flame appearance and instructions on installation after venting is completed MAXIMUM VERTICAL VENTING MINIMUM VERTICAL VENTING 45 ELBOW TERMINATION CAP TERMINATION C...

Страница 27: ...lame appearance and instructions on installation after venting is completed Horizontal sections require 1 4 6 mm rise for every 12 305 mm of travel For each additional elbow used after the first elbow...

Страница 28: ...on re strictor recommendations depending on burner flame appearance and instructions on installation after venting is completed IMPORTANT The Kozy Heat wall pass thru part 800 WPT or 800 WPT2 must be...

Страница 29: ...the four slots B securing it in place 9 Gently pull 5 8 pipes down to the top of extension kit or top of fireplace if no extension kits were used 10 Place a bead of sealant outside 5 flex pipe collar...

Страница 30: ...ft 914 mm horizontally from the centerline of the regulator I Gas Service regulator vent outlet 3 ft 914 mm J Non mechanical air supply inlet to building or the combustion air inlet to any other appl...

Страница 31: ...ROOF PITCH X 12 H minimum MINIMUM HEIGHT FROM ROOF TO LOWEST DISCHARGE OPENING APPROVED CAP APPROVED VENT PIPE DISCHARGE OPENING 8 MIN IF VENT IS CLOSER THAN 8 IT MUST TERMINATE AT LEAST 2 HIGHER THA...

Страница 32: ...ow instructions included with conversion kit NOTE Log numbers are located on the bottom of each log Refer to following instructions and illustrations for proper placement CAUTION Do not place logs dir...

Страница 33: ...AGE 32 STEP 4 STEP 3 9 8 Position two base logs 6 and 4 log onto burner as shown above DO NOT ALLOW LOGS TO COVER THE BURNER PORT HOLES Position logs 8 9 onto base logs and log grate The 8 log is plac...

Страница 34: ...own 7 6 5 LOG SET INSTALLATION PAGE 33 STEP 5 Randomly place Klinkers in this area Do not place Klinkers directly on burner ports Use a steel or stiff bristle nylon brush to distribute Rock Wool Ember...

Страница 35: ...lot shield and ember log refractory 8 Remove pilot shield 9 Remove screws securing front left and back right log grate legs Remove burner log grate assembly from firebox by lifting front of burner ass...

Страница 36: ...Reinstall log set Pages 31 33 8 Reconnect gas line to manual shut off valve 9 Model PRC 36 Reconnect any wall switch remote control or thermostat wires to the top bottom terminals on the gas valve Mod...

Страница 37: ...hood clips PAGE 36 Thread screws into nuts on each end of grill and secure to lower grill opening UPPER LOUVER HOOD LOWER GRILL INSTALLATION REMOVAL INSTALLATION REMOVAL C Partially thread 2 screws in...

Страница 38: ...VALVE TERMINALS GAS CONTROL KNOB PIEZO IGNITOR HI LO FLAME ADJUSTMENT KNOB ON OFF ROCKER SWITCH ELECTRODE PILOT HOOD THERMOPILE THERMOCOUPLE PILOT SHIELD PRC 36 VALVE PILOT ASSEMBLY COMPONENTS PAGE 37...

Страница 39: ...DUE TO HIGH SURFACE TEMPERATURES KEEP CHILDREN CLOTHING AND FURNITURE AWAY This appliance needs fresh air for safe operation and must be installed so there are provisions for adequate combustion and...

Страница 40: ...rmation on the front cover and on the previous page of this installa tion manual If you don t smell gas go to the next step B Locate pilot follow metal tube from gas control The pilot is located insid...

Страница 41: ...p off wall switch or adjust setting on the thermostat or remote control NOTE The pilot will stay lit H Turn the pilot off by pushing in and turning the gas control knob to the OFF position DO NOT FORC...

Страница 42: ...switch to OFF 7 Disconnect manometer hose and tighten screw clockwise Screw should be snug do not over tighten 8 Attach manometer to manifold pressure tap to verify that it is completely sealed Manome...

Страница 43: ...ODE THERMOPILE PILOT PAGE 42 PIEZO MOTOR GAS CONTROL KNOB INLET PRESSURE TAP OUTLET PRESSURE TAP LED FUEL CONVERSION PLUG ANTENNA PILOT ADJUSTMENT SCREW THERMOPILE MOTOR COVER WHITE DOTS FAN TERMINALS...

Страница 44: ...O HIGH SURFACE TEMPERATURES KEEP CHILDREN CLOTHING AND FURNITURE AWAY This appliance needs fresh air for safe operation and must be installed so there are provisions for adequate combustion and ventil...

Страница 45: ...or three pushes on the piezo igni tor Hold the knob for about one 1 minute after the pilot is lit Release knob and it will pop back out Pilot should remain lit If it goes out repeat steps A C D Push...

Страница 46: ...ceiver valve will be at the highest setting LOCAL SETTING Turn control knob clockwise to the PILOT position REMOTE SETTING The TR8220A transmitter can shut off the main burner and fan However the cont...

Страница 47: ...ch manometer to pressure tap using a 1 4 I D hose 4 Turn gas control knob to ON Note manometer reading 5 Disconnect manometer hose and tighten screw clockwise Screw should be snug do not over tighten...

Страница 48: ...does not receive a signal within 6 hours from the transmitter The negative leads white must be connected to the terminals marked with white dots LED TROUBLESHOOTING In normal operation LED blinks onc...

Страница 49: ...transmitter in a heated living space to make sure the main burner is not on continuously ON Mode With the control in the ON mode the flame and fan levels and the delay timer are changed with the UP a...

Страница 50: ...with black tips Open venturi setting slightly Open too far Blue flames Close venturi setting slightly NOTE IF SOOT IS PRESENT CHECK LOG POSITIONING BEFORE ADJUSTING BURNER VENTURI LOGS MUST NOT BLOCK...

Страница 51: ...ication is necessary remove restrictor by pulling it down and out of 5 exhaust pipe 5 Reinstall baffle by resting baffle front above flange along inside top of firebox opening Tip baffle back against...

Страница 52: ...ted at the inside top of the firebox and can be viewed through the glass The damper control is located under the firebox To reduce the amount of heat entering the room raise the damper control up and...

Страница 53: ...BY QUALIFIED SERVICE PERSON THE APPLIANCE SHOULD BE INSPECTED BEFORE USE AND ANNUALLY BY A QUALI FIED SERVICE PERSON MORE FREQUENT CLEANING MAY BE REQUIRED DUE TO EXCESSIVE LINT FROM CARPETING BEDDING...

Страница 54: ...STRUCTIONS A Check that pilot flame impinges on thermocouple Clean and or adjust pilot for maximum flame impingement B Ensure the thermocouple connection at gas valve is fully inserted and tight hand...

Страница 55: ...are faulty or connections are bad TROUBLESHOOTING PRC 36 only BURNER WILL NOT LIGHT FREQUENT PILOT OUTAGES A Pilot shield not installed B Pilot flame too high or too low causing pilot safety to drop...

Страница 56: ...n horizontal vent 1 4 6 mm rise per foot is required on horizontal venting E Inner vent pipe leaking exhaust gases back into firebox Check for leaks Repair if necessary F Improper vent cap installatio...

Страница 57: ...trol the main burner and fan Does transmitter change levels of flame height fan speed and set temperature Set levels of flame height and fan to 0 to shut off main burner and fan If the manual switch i...

Страница 58: ...n tank Check LP propane tank Refill if necessary PILOT WILL NOT STAY LIT AFTER CAREFULLY FOLLOWING LIGHTING INSTRUCTIONS A Check that pilot flame impinges on thermopiles Clean and or adjust pilot for...

Страница 59: ...T AND BURNER EXTINGUISH WHILE IN OPERATION C Improper pitch on horizontal vent 1 4 6 mm rise per foot is required on horizontal venting D Inner vent pipe leaking exhaust gases back into firebox Check...

Страница 60: ...641 www kozyheat com REPLACEMENT PARTS LIST PAGE 59 GRILL REPLACEMENT PRC 200 Upper Hood PRC 201 Lower Grill PRC 200L Upper Hood Louver REFRACTORY PANELS Sandstone MTK G900 3 pc Refractory Panel Set M...

Страница 61: ...PAGE 60...

Страница 62: ...PAGE 61...