Determine exact position of fireplace, including hearth height, width, and depth, (if applicable). If possible, place fireplace in such a manner that
vent termination will be placed between two studs, eliminating the need for additional framing.
If masonry is to be used (optional), prepare necessary foundation for the masonry load. When masonry construction is being used, a lintel must
be used over top of fireplace to support the added weight.
FRAMING
WALL ROUGH OPENING
IMPORTANT: Framing dimensions should allow for wall covering thickness and fireplace facing materials.
If using a hearth, adjust rough opening size as necessary to maintain at least minimum clearance requirements.
IMPORTANT: Non-combustible material man be applied around (but not directly to) fireplace face.
(
APPLIES TO BOTH HORIZONTAL AND VERTICAL VENTING TERMINATIONS)
32-5/8” (829 mm) High* x 19-3/4”(502 mm) Wide x 14-7/8” (378 mm) Deep.
* Header must be in the „up‟ position to maintain proper clearances from vent system to combustibles.
MINIMUM ENCLOSURE HEIGHT: 47” (1.19 m) from base of fireplace.
Build hearth to desired size and height. If a hearth extension is desired, combustible material may be used. If carpeting or other combustible
flooring is desired in front of fireplace, fireplace bottom must level or above flooring material level.
WARNING
:
Install fireplace on hard metal or wood surface extending full width and depth of fireplace.
Minimum platform size: 19-3/4” (502 mm) wide x
14-7/8” (378mm) deep.
FIRE HAZARD: Do NOT install directly on carpeting, vinyl, or any combustible material other than wood.
PAGE 8
IMPORTANT: Header must be positioned „up‟ to maintain proper
clearances from vent system to combustibles.
14-
7/8”
(378 mm)
19-
3/4”
(502 mm)
47”
(1.19 m)