This fireplace is manufactured for use with Natural Gas. An LP conversion kit (#OCK-A60L-IPI), is included with this fireplace.
Follow instructions included with conversion kit if converting to LP gas.
#NCL-195
NATURAL GAS
LP GAS
MINIMUM INLET GAS PRESSURE
5.0 inches W.C. (7.0 W.C. recommended)
11.0 inches W.C. (recommended)
MAXIMUM INLET GAS PRESSURE
10.5 inches W.C.
13.0 inches W.C.
ORIFICE SIZE
#52
#60
INPUT BTU/hr.
12,500
12,500
MINIMUM INPUT BTU/hr.
4,500
4,500
EFFICIENCY
66.27%
62.15%
AFUE
65.20%
60.83%
GAS LINE CONNECTION
GAS CONVERSION
PAGE 13
CAUTION: Installation of the gas line must only be done by a qualified person in accordance with local building codes, if any.
If not, follow ANSI 223.1.
Commonwealth of Massachusetts: Installation must be done by a licensed plumber or gas fitter.
IMPORTANT:
The efficiency rating of this appliance is a product of thermal efficiency rating determined under continuous operating
conditions and was determined independently of any installed system.
NOTE: A listed (and Commonwealth of Massachusetts approved) 12” (13 mm) T- handle manual shut-off valve and flexible gas connector
(included) are connected to the 1/2” (13 mm) control valve inlet. If substituting for these components, please consult local codes for
compliance.
NOTE: This fireplace is equipped with a 3/8”(10 mm) x 18” (457 mm) long flexible gas connector and manual shut-off valve. The gas line
should be run to the point of connection where the shut-off valve and flexible gas line will connect.
NOTE: The appliance and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing
of that system at pressures in excess of ½ psi.
NOTE: The appliance must be isolated from the gas supply piping system by closing its individual manual shut-off valve during any
pressure testing of the gas line at test pressures equal to or less than ½ psi (3.5 kPa).
NOTE: For high altitude installations, consult the local gas distributor or the authority having jurisdiction for proper rating methods
.
ATTENTION: The conversion shall be carried out in accordance with the requirements of the provincial authorities having jurisdiction and in
accordance with the requirements of the ANSI Z223.1 installation code.