HORIZONTAL VENT HEAT SHIELD INSTALLATION
Slide slots under screws.
Tighten screws
VENTING
#800-WPT / #800-WPT2 WALL PASS-THRU KITS INSTALLATION
12-1/2” (318 mm) HIGH x 10-7/8” (276 mm) WIDE
A. Measure wall thickness; cut insulation panel
(included) this length.
B. Install wall pass-thru section marked #1 (with
3/8” (10 mm) flange) into framed opening. Secure to
interior wall with screws (not provided).
C. From the exterior, place insulation between flange and
top of framed opening in wall pass-thru section #1.
D. Install section marked #2 of wall pass-thru into
framed opening, overlapping metal sections as
necessary to accommodate wall thickness. Secure
to exterior wall with screws (not provided).
FRAMING DIMENSIONS FOR KOZY HEAT WALL PASS-THRU KITS
INSULATION
HEAT SHIELD MUST BE FLUSH
WITH WALL PASS -THRU.
WARNING: MAINTAIN ALL CLEARANCES AS STATED IN THIS INSTALLATION MANUAL.
PAGE 16
3/8” (10 mm) FLANGE MUST BE
ON INSIDE WALL.
1. Install 90-
degree elbow per manufacturer‟s installation instructions.
2. Loosen, but do not remove (2) screws at top of fireplace.
3. Slide (2) slots on horizontal vent heat shield under screws. Re-tighten screws to secure in place.
Loosen, but do not remove screws
IMPORTANT: THE HORIZONTAL VENT HEAT SHIELD MUST BE INSTALLED WHEN USING A 90-DEGREE ELBOW TO
HORIZONTALLY POSITION VENT SYSTEM.
IMPORTANT: KOZY HEAT WALL PASS-THRU, PART #800-WPT (4-1/2” (114 mm) - 6-1/2” (165 mm) ) WALL THICKNESS OR
#800-WPT2 (6-1/2” (165 mm) - 12-1/2” (318 mm) ), MUST BE USED ON ALL HORIZONTAL VENT RUNS.