5.4. Temperature Sensors Installation
The supply air temperature sensor B1 (5.4 a Picture) is mounted in the air duct in a projected place for it; after
electric heater or cooler section (if provided). The minimal distance from the air vent of the unit up to the sensor
should be not less than a diagonal of rectangular connection.
The water temperature sensor B5 (5.4 b Picture) is mounted on the water pipe by screwing it into the provided
hole. The sensor must be thermo insulated!
Supply air temperature sensor B1
5.4 a Picture
Water temperature sensor B5
5.4 b Picture
5.5. Requirements for the installation of the control panel
1. The control console should be installed in a room where the following conditions are ensured:
1.1. Ambient temperature: 0 °C ... 40 °C;
1.2. Relative humidity range: 20 % ...80 %;
1.3. Protection against vertical dripping of water (IP X2).
2. Installation height: at least 0.6m from the floor.
3. Control panel connection: designed through the hole in its back side.
4. The panel is fixed by drilling two holes on the fixation surface.
5.6. Control panel connection
The control panel is connected to the controller box (see Picture 5.3). The length of the cable for connecting the
panel with the unit may not exceed
150 m
. The cable type is indicated on the electrical diagram of the unit.
View of the control console
5.6 Picture
When closing the console cover, do not bend the springs inside the con-
sole; otherwise, the console buttons may fail to operate! Prior to connect-
ing the control console, supply voltage must be disconnected!
Control panel connection and other cable thicknesses are specified in the
wiring diagram!