6.11. Control of air handling units through a web browser
You may not only monitor the operation of VERSO air handling units and the functionality of their individual
components, change settings and activate extra functions by means of control panel but also by your computer.
All you need is to connect the unit to the computer, local area network or the Internet using a network cable.
Standard CAT 5
network cable
How to connect the unit directly to your computer:
1. Plug one end of the network cable into the controller port on the unit (see Picture 5.3 a) and the other end to
the computer.
2. Go to the properties of your network card and enter IP address, e. g. 192.168.0.200, and subnet mask
255.255.0.0.
3. Open the web browser on your computer and disable all proxy servers in the settings.
4. In the address bar of your web browser enter the IP address associated with the air handling unit; the default
IP address is 192.168.0.50. You can change it at any time on the control panel or from web browser (see con-
nection settings).
Note:
It is recommended to download the latest version of your web browser before use.
5. If the connection is successful, a window prompting to enter your user name and password appears:
Note:
the user name is
“user”
. The initial password is also
“user”
; after logging in, the user can later change
the password to any other of his/her choice (see user interface settings).
In case you forget your new password, you can restore the initial password
“user”
at any time through control panel settings.
6.12. Additional control options
6.12.1. Combined water coil control
For the air handling unit with the combined water coil (Combi-coil – heater and cooler in one) the control of the
mixing valve actuator is provided both under the air heating and cooling modes. The actuator is connected to the
control terminals of the heating circuit and operates only under the heating mode by default. However upon trans-
fer of the feedback signal confirming that there is cold water within the circulation system to the control terminals
(IN4) of the external control (e.g., by connecting additional device: thermostat, switch, etc.), the air cooling function
will be activated, and the mixing valve actuator (TG1) will be controlled under the air cooling mode.