UAB KOMFOVENT we reserve the right to make changes without prior notice
KBP2-18-10
2.7. Liquid coupled heat exchanger
section
Temperature efficiency – up to 63%. In this system,
the warming part of heat exchanger is in the supply air
stream and the cooling part – in the exhaust stream.
Both parts of the heat exchanger are connected with
pipes to a common circuit, which circulates a mixture
of water and glycol. This type of equipment is used only
where air flows must be completely separated from
each other, as well as when, taking into account the
characteristics of the project, or other requirements,
they must be on different floors.
Heat exchangers are made of copper tubing and al-
uminium fins.
2.8. Water-heater section
Water air heaters
Normally are used with aluminium fins and copper
pipes. Can be equipped with thread joint to connect
freezing sensor.
The heater can be removed from the inspection side,
by disconnecting the coolant pipes and unscrewing the
panel mounting screws.
All heaters are mounted on rails, therefore they are
easy to remove.
• Maximum pressure – 21 bar.
• Maximum water tempe100ºC.
(by special order up to + 130ºC).
• Heated air temperature up to +40ºC.
KLASIK
size
B
H
b
h
mm
1
1015
555
700
300
2
1155
655
900
400
3
1305
710
1000
500
4
1505
810
1200
600
5
1745
955
1400
700
6
1905
1010
1600
800
7
2140
1130
1800
900
8
2310
1265
2000
1000
9
2310
1490
2000
1200
10
2310
1570
2000
1300
11
2590
1650
2200
1400
12
2890
1830
2500
1600
B
b
h
H
For ventilation units operated outdoors when the ambient air temperature t
amb
< 0°C,
it is necessary to use water-ethylene glycol mixture to prevent freezing of water
and damage to the heat exchanger.