![Komfovent KLASIK CF Series Скачать руководство пользователя страница 6](http://html.mh-extra.com/html/komfovent/klasik-cf-series/klasik-cf-series_installation-manual_1991517006.webp)
6
UAB KOMFOVENT we reserve the right to make changes without prior notice
KBP2-18-10
2.1. Filter section
Air is cleaned of various origin and size particles of
dust in the ventilation units with synthetic and glass fib-
er filters. 99.9% (by number) of outdoor airborne parti-
cles are smaller than 1 mm. By mass, the said particles
make up 30% of the airborne dust. Thus, if the air from
the city is supplied to public and residential buil dings,
M5-F7 class filters are sufficient to achieve the hy-
giene standards of air cleanliness. In areas where dust
content is low (e.g. forested places, areas away from
roads, industry, etc.) air supplied to the rooms should
be cleaned less extensively.
G3, G4, or M5 prefilters should be used upstream
F8, or at higher-end filters.
Air supplied to industrial facilities usually only has
to be cleaned slightly (G3, G4 class – if there are no
special technological requirements)
Air filtering protects ventilation equipment against
contamination, and prolongs the service life.
KLASIK
size
B
H
b
h
L
1
L
2
L
3
L
4
mm
1
1015
555
700
300
400
600
700
500
2
1155
655
900
400
400
600
700
500
3
1305
710
1000
500
400
600
700
500
4
1505
810
1200
600
400
600
700
500
5
1745
955
1400
700
500
600
700
500
6
1905
1010
1600
800
500
600
700
500
7
2140
1130
1800
900
500
600
700
500
8
2310
1265
2000
1000
500
600
700
500
9
2310
1490
2000
1200
500
600
700
500
10
2310
1570
2000
1300
500
600
700
500
11
2590
1650
2200
1400
540
640
740
540
12
2890
1830
2500
1600
540
640
740
540
1 – Filters section with compact filter, 2 – Filters section with pocket filter, 3 – Filters section with carbon filter,
4 – Filters section with HEPA filter.
Unit weight is indicated in the technical offer, attached to the passport of the unit.
b × h
800*
B
H
* 11, 12 size L = 840 mm.