2.5. Plate heat exchanger section
Plate-type heat exchanger
Used in KLASIK P series units.
Temperature efficiency factor – up to 70% (in wet con-
ditions). The heat exchanger is sealed, the two air
streams are separated, contaminated air heat recov-
ery is optional.
Aluminium plate heat exchangers are used in the
units.
For recuperated heat regulation and protection of
frost, the heat exchanger is provided with the air by-
pass valve. Each unit with a plate heat exchanger is
equipped with a steel drip pan for condensate collec-
tion and drainage.
KLASIK
size
B
H
L
L*
mm
1
1015
1110
850
1000
2
1155
1310
1140
1250
3
1305
1420
1140
1250
4
1505
1620
1140
1250
5
1745
1910
1440
1600
6
1905
2020
1740
1850
7
2140
2260
1740
1850
8
2310
2530
1740
1850
9
2310
2980
2290
2150
10
2310
3140
2300
2420
11
2590
3300
2350
2420
12
2890
3660
2650
2750
* with the drip pan on the top
L
B
H
The difference between the supply and exhaust air volume must be 0.66 ... 1.5!
Otherwise, the specifications are only theoretical!
When the temperature after the heat exchanger is ≤ 0°C, it is necessary to provide
protection from freezing, for example, electric heater upstream the heat exchanger.
When the air flow exceeds 2.5 m/s, the drop tray is recommended!