22
UAB KOMFOVENT we reserve the right to make changes without prior notice
KBP2-18-10
Unit size
A, mm
A min, mm
B, mm
H, mm
1
1015
800
500
500
2
1155
800
500
500
3
1305
800
500
500
4
1505
900
500
500
5
1745
900
500
500
6
1905
900
500
500
7
2140
1000
500
500
8
2310
1150
500
500
9
2310
1150
500
500
10
2310
1350
500
500
11
2590
1350
500
500
12
2890
1500
500
500
3.3. Selection of mounting location
The ventilation unit, depending on its type, may be in-
stalled both indoors or outdoors. Some of the devices
can be ceiling mounted. When selecting an installa-
tion or mounting location, it is mandatory to foresee
sufficient and security compliant access space for re-
pair and maintenance operations. The unit must be in-
stalled in a way so that it may be partially or fully dis-
assembled, if needed (e.g. in case of heavy repairs).
Minimum service space Amin defines an area which
may not contain any stand-alone or immovable devic-
es, equipment, partitions, structure or furniture. This
space is sufficient for service and filter replacement
works. For repair and replacement of components, ac-
cess space A, equal to the width of the device, shall be
ensured in front of the device.
A recommended space for the unit maintenance
A
min
minimal necessary space for the unit operation
H free space over the installed air handling unit
B recommended space behind the air handling unit
A
A min
B
H
If the device is not equipped with height adjustable
feet, it must be installed on a flat base. The base can be
made from poured reinforced concrete or from pre-fab-
ricated metal structures. Vibration dampening gaskets
must be installed between the unit and its installation
base. When the unit is not equipped with an installation
frame or height adjustable feet, it should be fixed to the
base using metal angle brackets and rubber vibration
dampening gaskets. Units mounted to ceilings or other
special structures must be fixed using threaded bars
and vibration dampening holders. During installation,
both suspended and stationary units must be levelled
in respect to the horizon. Deviations shall not exceed
0.3mm for 1m in the longitudinal direction and 0.5mm
for 1m in the transverse direction.