17
UAB KOMFOVENT we reserve the right to make changes without prior notice
KBP2-18-10
2.12. Sound attenuator section
Where a ventilated room is subject to extremely high de-
mands on noise levels, UAB KOMFOVENT makes ven-
tilation units with integrated noise suppression sections.
The housing of sound suppression sections is the
same as in ventilation units – with full insulation and a
high level of noise suppression.
The suppression section is equipped with partitions
filled with noise absorbing loose mineral wool panels,
which are overlaid with a thin layer of polypropylene
fibers (to prevent dust), and perforated galvanized
steel sheets.
Partition number and size depends on the require-
ments of the noise reduction level.
2.13. Humidification section
Low-pressure steam humidifier or adiabatic humidifier
can be used.
Air humidification
with low pressure water steam
is
cost-effective, hygienic and highly accurate method
of air humidification. Related air humidity may be up
to 90%. The humidification section is equipped with a
stainless steel bath and a drain pipe.
There are 2 possible types of the
adiabatic humidi-
fier
:
– by spraying water;
– using a porous material.
Downstream the humidifier, moisture in the air remains
only in the form of steam. The special design of the
device does not allow water droplets to pass – each
humidification section is equipped with polypropylene
drop catchers.
Water is removed through a stainless steel drain tray
and a copper pipe.
Air humidifier after using a
porous material
Air humidification with
low pressure water
steam
Noise suppression of 45 mm thick walls of ventilation
units
Frequency
(Hz)
63 125 250 250 1000 2000 4000 8000
Suppres-
sion (dB)
11 13 17 28 30
34
42
46
Noise suppression of 50 mm thick walls of ventilation
units
Frequency
(Hz)
63 125 250 250 1000 2000 4000 8000
Suppres-
sion (dB)
13 15 20 28 28
25
29
30
For hygienic purposes, it is advisable to provide the
automatic periodic flushing function of the humidifica-
tion section. During section flushing air is not supplied
to the ventilation system. After washing, water is comp-
letely drained from the drain bath.
For air humidification with water, the must
have a water preparation system!