4-30 Controller Troubleshooting
TP-5672 11/95
Yes
Yes
No
Yes
Yes
Yes
Yes
Yes
Yes
No
No
Yes
No
No
No
No
No
Yes
Is the Load/No Load
selector switch in the
NO LOAD position?
Check for continuity between
terminals TB-DC1-10 and
TB-DC1-32 of the power supply
board. Is there continuity?
Place the Load/No Load
selector switch into the
NO LOAD position.
Is there continuity across the
Load/No Load selector
switch when it is in the
NO LOAD position?
Do pins 11 and 15 on
plug P3 short when the
plant exerciser is active?
Place a jumper across terminals
21 and 31 on TB-DC1 of the
power supply board. Does the
generator set start?
Is the plant exerciser
programmed correctly in
index 8? See TP-5664 for
programming information.
Do pins 11 and 15 on
plug P2 short when the
plant exerciser is active?
Place a jumper across the
start terminals 3 and 4 on
the power conversion unit.
Does the generator set
start?
Replace the
Load/No Load
selector switch.
Remove the leads from terminals
TB-DC1-10 and TB-DC1-32 of
the power supply board. Is there
continuity from terminals
TB-DC1-10 to TB-DC1-32 of the
power supply board?
Replace the
logic board.
Replace the leads from
terminals TB-DC1-10
and TB-DC1-32 of the
power supply board.
Replace the
logic board.
Replace the ribbon
cable between
plugs P2 and P3.
Replace the
logic board.
Reprogram the
plant exerciser.
Refer to TP-5664
for programming
instructions.
Check the engine start
circuit for an open circuit.
Replace the wiring harness
between TB-DC1 and the
power conversion unit.
Yes
No
Is the Plant Exer jumper
installed in JP1 on the logic
board?
Install the Plant Exer jumper
on JP1 and power down the
controller for 1 minute
mininum.
In Index 11 is Plant
Exerciser enabled?
Troubleshoot
shunt-jumper
controlled options.
See Figure 4-18.
No
No
Figure 4-29. Troubleshooting— Accessory 23-G, plant exerciser, does not work (unloaded exercise)