![Kohler M340+ Скачать руководство пользователя страница 114](http://html1.mh-extra.com/html/kohler/m340/m340_service-and-parts-manual_1989901114.webp)
5-53
Accessory Troubleshooting
TP-5672 11/95
LC
TBAC1--LC
TBAC1--LA
LA
LC
BC--AC2
BC--AC1
LA
TB--AC1
MICROCONTROLLER
TB--DC1
34
33
32
31
30
29
28
27
26
25
24
23
22
21
20
19
18
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
17
ECS
EAS
NCS
NAS
LC
LB
LA
EC
EB
EA
NC
NB
NA
Battery
AC
2
1
AC
Charger
Wire Code Example
S10--13— 201
Device Name
Wire Number
Device Terminal
Number
5604534
+
--
D.C. To Battery
Figure 5-59. Wiring Diagram— Option DD-24-A and DD-24-B, Battery charger
Check the battery charger connections to the
battery for correct polarity (positive on positive,
negative on negative). Is the polarity correct?
Turn off the AC supply to the
battery charge. Are the battery
terminals clean and tight?
Is there rated line-to-line voltage
at the AC input terminals of the
battery charger?
Is there rated line to line voltage
between terminals TB-AC1-LA and
TB-AC1-LC of the power supply board?
Check if the AC input and
DC output fuses are blown.
Are the fused blown?
Power is not available. Check
the wiring harness to contactor.
Replace the leads from TB-AC1-LA
and TB-AC1-LC of the power supply
board to the battery charger.
Replace the
blown fuse.
Replace the
battery charger.
Correct charger
leads to battery.
Clean and tighten
the battery terminals.
Yes
Yes
Yes
No
No
No
No
No
Yes
Yes
Figure 5-60. Troubleshooting— Option DD-24-A and DD-24-B, No ammeter reading on battery charger