![Kohler M340+ Скачать руководство пользователя страница 28](http://html1.mh-extra.com/html/kohler/m340/m340_service-and-parts-manual_1989901028.webp)
4-1
Controller Troubleshooting
TP-5672 11/95
Section 4. Controller Troubleshooting
The following section will assist in solving common
problems with the M340+ controller. Note any optional
accessories that may have been furnished on this switch
and review their operation in section 5— Accessory
Troubleshooting.
No
Yes
Yes
No
No
Yes
No
Yes
Yes
No
Yes
No
No
Yes
Yes
No
Yes
No
Yes
No
No
Yes
Yes
No
No
Yes
Yes
No
Yes
Yes
No
Is the LCD screen blank
and no LEDs illuminated?
Is there normal source
voltage between terminals
TB-AC1-NA and TB-AC1-NC
of the power supply board?
Is there 19 vac between terminals
TB-AC1-NAS and TB-AC1-NCS of
the power supply board?
Is a battery connected to terminals
TB-DC1-29 and TB-DC1-34 of the
power supply board?
Is there rated battery voltage
between terminals TB-DC1-29
and TB-DC1-34 of the power
supply board?
Is there from 12 to 30 vdc
between terminals
TB-DC1-23 and TD-DC1-34
of the power supply board?
Is there 10 vdc between pin P2-13
of plug 2 and terminals TB-DC1-34
of the power supply board?
Is there 10 vdc between terminals
TB-DC1-30 and TB-DC1-34 of
the power supply board?
Is there an optional
load-shed board
installed?
Recheck the voltage at terminals
TB-DC1-23 and TB-DC1-30 of the
power supply board, and pin P2-13
of plug 2. Are the voltages correct?
Is an optional remote
communications board
installed?
Recheck the voltage at terminals TB-DC1-23
and TB-DC1-30 of the power supply board, and
pin P2-13 of plug 2. Are the voltages correct?
Recheck the voltage at terminals TB-DC1-23
and TB-DC1-30 of the power supply board, and
pin P2-13 of plug 2. Are the voltages correct?
Recheck the voltage at terminals TB-DC1-23
and TB-DC1-30 of the power supply board, and
pin P2-13 of plug 2. Are the voltages correct?
Disconnect the
load-shed board.
Replace the
load-shed board.
Disconnect the
communications
board.
Replace the remote
communication board.
Replace the
logic board.
Replace the logic board.
Troubleshooting
complete.
Check the normal source
and contactor-to-power
supply board wiring harness
for open or shorted leads.
Replace the power
supply board.
Check battery and wiring
from battery to assembly
for open of shorted leads.
Disconnect the logic board.
Disconnect the status panel
board.
Replace the power supply board.
Replace the
logic board.
Yes
Figure 4-1. Troubleshooting— Power to the system