![Kohler M340+ Скачать руководство пользователя страница 42](http://html1.mh-extra.com/html/kohler/m340/m340_service-and-parts-manual_1989901042.webp)
4-15
Controller Troubleshooting
TP-5672 11/95
Programming Mode Not-In-Off
For location of pushbuttons, switches, LEDs, and keys
referred to in this section, see Figure 2-1.
The Programming Mode Not-In-Off LED signals the
status of the Programming-Mode key switch. The three
programming modes are Remote, Off, and Local. When
the Programming-Mode key is set to Local programming
mode, the Programming Mode Not-In-Off LED should be
flashing. When the Programming-Mode key is set to
Remote programming mode, the Programming Mode
Not-In-Off LED should be on steadily. When the
Programming-Mode key is set to Off, the Programming
Mode Not-In-Off LED should be off. See Figure 4-10. If
any of these cases are not true, check the
Programming-Mode key switch for proper wiring and
operation. If the problem still exists, replace the logic
board assembly.
Programming Mode Switch
“New”style switch— green plastic body
Position
Contacts Closure
Remote
1-8
Off
1-3
Local
3-5
Programming Mode Keyswitch (”New”style)
3
5
1
8
Remote
TB3
5604410
Local
C
Programming Mode Switch
“Old”style switch— blue plastic body
Position
Contacts Closure
Remote
7-6
Off
7-1
Local
1-3
Programming Mode Keyswitch (”Old”style)
1
3
7
6
Remote
TB3
Local
C
Figure 4-10. Wiring Diagram— Programming Mode Keyswitch