5-28 Accessory Troubleshooting
TP-5672 11/95
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
No
No
Yes
No
Yes
No
Is the emergency
source available?
Is there rated line-to-line
emergency source voltage
between terminals
TB-AC1-EA and TB-AC1-EC
of the power supply board?
Is there a transformer wired
between terminal TB-AC1-EA
of the power supply board
and the frequency meter?
Is there rated line-to-line
voltage at the primary
windings of the transformer?
Is there 120 vac at the
secondary winding of
the transformer?
Is there 120 vac between the
two frequency meter terminals?
Is the in-line fuse between
the secondary side of the
transformer and the
frequency meter blown?
Is there rated line-to-line
voltage between the two
frequency meter terminals?
Is the in-line fuse between
terminal TB-AC1-EA of the
power supply board and the
frequency meter blown?
Accessory 18-G only
displays emergency
source frequency.
Refer to Source-Available,
Emergency Error Troubleshooting.
Replace the leads from
terminals TB-AC1-EA and
TB-AC1-EC of the power supply
board to the transformer.
Replace the transformer.
Replace the
frequency meter.
Replace the fuse
between the secondary
side of the transformer
and the frequency meter.
Replace the leads
between the transformer
and the frequency meter.
Replace the fuse between
terminal TB-AC1-EA of the
power supply board and
the frequency meter.
Replace the leads
between the transformer
and the frequency meter.
Replace the
frequency meter.
Yes
Yes
Figure 5-33. Troubleshooting— Option DD-18-G, Meter will not display frequency