4-28 Controller Troubleshooting
TP-5672 11/95
TB--DC1
MICROCONTROLLER
TB--AC1
Programming shunt (294634)
34
33
32
31
30
29
28
27
26
25
24
23
22
21
20
19
18
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
17
ECS
EAS
NCS
NAS
LC
LB
LA
EC
EB
EA
NC
NB
NA
OVRIDE
DELAY
EXER
FREQ
SEQUENCER
MANUAL
TIME
PLANT
VOLT/
PHASE
IN--PHASE
NO
110
1
EXERCISOR SELECT
1 — 2
2
S11
W/LOAD
S11
LOAD
132
560453
MONITOR
DELAYS
OFF
must be installed to activate accessory
Figure 4-26. Wiring Diagram— Plant exerciser, option DD-23-G
Yes
No
Yes
No
No
No
Yes
Yes
Yes
No
No
Yes
Yes
Is the Plant Exer jumper
installed in JP1 on the logic
board?
Do pins 11 and 15 on plug
P3 short when the plant
exerciser is active?
Place a jumper across terminals 21
and 31 on TB-DC1 of the power supply
board. Does the generator set start?
Do pins 11 and 15 on plug
P2 short when the plant
exerciser is active?
Is the plant exerciser programmed
correctly in index 8? See TP-5664
for programming information.
Place a jumper across start
terminals 3 and 4 on the power
conversion unit. Does the
generator set start?
Replace logic board.
Replace the ribbon cable
between plugs P2 and P3
Replace logic board.
Reprogram the plant
exerciser. Refer to TP-5664
for programming instructions.
Check the engine start
circuit for an open circuit.
Replace the wiring harness
between TB-DC1 and the
power conversion unit.
Install the Plant Exer jumper
on JP1 and power down the
controller for 1 minute
mininum.
In Index 11 is Plant
Exerciser enabled?
Troubleshoot
shunt-jumper
controlled options.
See Figure 4-18.
No
Figure 4-27. Troubleshooting— Accessory 23-C, plant exerciser, does not work