4-31
Controller Troubleshooting
TP-5672 11/95
No
No
Is the
Load/No Load
selector switch in
the LOAD position?
Place the
Load/No Load
selector switch into
the LOAD position.
Check for continuity from
TB-DC1-10 to the
Load/No Load selector
switch. Is there continuity?
Replace the lead from TB-DC1-10 to
the Load/No Load selector switch.
Check for continuity from
terminal TB-DC1-32 of the
power supply board to the
Load/No Load selector
switch. Is there continuity?
Is there continuity across
the Load/No Load
selector switch ?
Replace the
Load/No Load
selector switch.
Replace the lead from terminal
TB-DC1-32 of the power supply
board to the Load/No Load
selector switch .
Do pins 11 and 15 on
plug P3 short when the
plant exerciser is active?
Place a jumper across terminals
21 and 31 on TB-DC1 of the
power supply board. Does the
generator set start?
Is the plant exerciser
programmed correctly in
index 8? See TP-5664 for
programming information.
Replace the
logic board.
Reprogram the plant
exerciser. Refer to TP-5664
for programming instructions.
Do pins 11 and 15 on
plug P2 short when the
plant exerciser is active?
Replace the
logic board.
Replace the ribbon cable
between plugs P2 and P3.
Place a jumper across the
start terminals 3 and 4 on the
power conversion unit. Does
the generator set start?
Check the engine start
circuit for an open circuit.
Replace the wiring harness
between terminal TB-DC1 of
the power supply board and
the power conversion unit.
Yes
No
Yes
No
No
Yes
Yes
Yes
No
No
Yes
Yes
No
No
No
Yes
Yes
No
Yes
Is the Plant Exer jumper
installed in JP1 on the logic
board?
Install the Plant Exer jumper
on JP1 and power down the
controller for 1 minute
mininum.
In Index 11 is the Plant
Exerciser enabled?
Troubleshoot
shunt-jumper
controlled options.
See Figure 4-18.
No
Figure 4-30. Troubleshooting— Accessory 23-G, plant exerciser, does not work (loaded exercise)