52 Section 2 Operation
synchronize to the bus after the time delay expires and
the warning occurs. Generator Management will start
another generator set if this warning occurs.
Fuel Tank Leak.
The fault lamp illuminates yellow and
the alarm horn sounds when the fuel tank signals a leak
of the inner tank. This fault requires an optional fuel tank
leak switch for the lamp to function.
Generator Frequency High.
The fault lamp illuminates
yellow and the alarm horn sounds when the generator
has an overfrequency condition. The output breaker
trips.
This condition can be caused by various
mechanical failures (loss of speed signal to ECU,
improperly controlled or inadvertent injection of
gaseous fuel etc.).
Generator Frequency Low.
The fault lamp illuminates
yellow and the alarm horn sounds when the generator
has an underfrequency condition. The output breaker
trips.
Generator Total Real Power High.
The fault lamp
illuminates yellow and the alarm horn sounds when the
generator encounters excessive load or a downstream
fault. The output breaker trips.
Generator Total Real Power Low.
The fault lamp
illuminates yellow and the alarm horn sounds when the
generator is no longer producing power (loss of fuel,
bearing failure, fuel system failure, ECU problem, or
speed bias connection failure on non-ECM engines).
The output breaker trips.
Ground Fault Input.
The fault lamp illuminates yellow
and the alarm horn sounds when a user-supplied
ground fault detector signals the controller.
High Battery Voltage.
The fault lamp illuminates yellow
and the alarm horn sounds when the battery voltage
rises above the preset level for more than 10 seconds.
Figure 2-4 shows high battery voltage specifications.
The high battery voltage feature monitors the battery
and battery charging system in the generator set
operating and off modes.
Engine Electrical
System Voltage
High Battery
Voltage Range
High Battery Voltage
Default Setting
24
26.4- 32.4
30
Figure 2-4
High Battery Voltage Specs
High Coolant Temperature.
The fault lamp illuminates
yellow and the alarm horn sounds when the engine
coolant temperature approaches the shutdown range.
The high coolant temperature warning does not function
during the preset inhibit time delay period after startup.
High Fail To Close Delay.
The fault lamp illuminates
yellow and the alarm horn sounds when the circuit
breaker did not close within the allocated breaker
closure time.
High Fail To Open Delay.
The fault lamp illuminates
yellow and the alarm horn sounds when the circuit
breaker did not open as quickly as the controller
expected.
High Fuel Level (diesel-powered models only).
The
fault lamp illuminates yellow and the alarm horn sounds
when the fuel tank level on diesel models approaches
near full. This fault requires an optional high fuel switch
and fuel tank for the lamp to function.
High Genset System Frequency.
The fault lamp
illuminates yellow and the alarm horn sounds when
another generator in the paralleling system has a lower
system frequency than this generator. The local display
shows System Frequency, FMI: High.
High Genset System Voltage.
The fault lamp
illuminates yellow and the alarm horn sounds when
another generator in the paralleling system has a lower
system voltage than this generator. The local display
shows System Voltage, FMI: High.
High Intake Air Temperature.
The fault lamp
illuminates yellow and the alarm horn sounds when the
engine intake air temperature approaches the shutdown
range.
High Lube Oil Temperature.
The fault lamp illuminates
yellow and the alarm horn sounds when the engine high
oil temperature approaches the shutdown range.
High Max. Close Attempts
The fault lamp illuminates
yellow and the alarm horn sounds when the circuit breaker
did not close, even after the controller attempted to close it
as many times as specified by the max. close attempts.
In IMO Tier2 Mode (IMO Tier III Models)
. The fault
lamp illuminates yellow and the alarm horn sounds to
inform the user that the engine ECM is currently running
in IMO Tier2 mode.
Содержание 300EFOZCS
Страница 8: ...TP 7126 5 20 8 Safety Precautions and Instructions Notes...
Страница 12: ...TP 7126 5 20 12 Maintenance and Service Parts Related Literature Notes...
Страница 44: ...TP 7126 5 20 44 Section 1 Specifications Notes...
Страница 80: ...TP 7126 5 20 80 Section 4 Troubleshooting Notes...
Страница 83: ...TP 7126 5 20 83 Section 5 Wiring Diagrams GM105387A A Figure 5 1 Wiring Diagram Sheet 1 of 5 GM105387A...
Страница 84: ...TP 7126 5 20 84 Section 5 Wiring Diagrams GM105387B A Figure 5 2 Wiring Diagram Sheet 2 of 5 GM105387B...
Страница 85: ...TP 7126 5 20 85 Section 5 Wiring Diagrams GM105387C A Figure 5 3 Wiring Diagram Sheet 3 of 5 GM105387C...
Страница 86: ...TP 7126 5 20 86 Section 5 Wiring Diagrams GM105387D A Figure 5 4 Wiring Diagram Sheet 4 of 5 GM105387D...
Страница 87: ...TP 7126 5 20 87 Section 5 Wiring Diagrams GM105387E A Figure 5 5 Wiring Diagram Sheet 5 of 5 GM105387E...
Страница 88: ...TP 7126 5 20 88 Section 5 Wiring Diagrams ADV9061A A Figure 5 6 Schematic Sheet 1 of 7 ADV9061A...
Страница 89: ...TP 7126 5 20 89 Section 5 Wiring Diagrams ADV9061B A Figure 5 7 Schematic Sheet 2 of 7 ADV9061B...
Страница 90: ...TP 7126 5 20 90 Section 5 Wiring Diagrams ADV9061C A Figure 5 8 Schematic Sheet 3 of 7 ADV9061C...
Страница 91: ...TP 7126 5 20 91 Section 5 Wiring Diagrams ADV9061D A Figure 5 9 Schematic Sheet 4 of 7 ADV9061D...
Страница 92: ...TP 7126 5 20 92 Section 5 Wiring Diagrams ADV9061E A Figure 5 10 Schematic Sheet 5 of 7 ADV9061E...
Страница 93: ...TP 7126 5 20 93 Section 5 Wiring Diagrams ADV9061F A Figure 5 11 Schematic Sheet 6 of 7 ADV9061F...
Страница 94: ...TP 7126 5 20 94 Section 5 Wiring Diagrams ADV9061G A Figure 5 12 Schematic Sheet 7 of 7 ADV9061G...
Страница 95: ...TP 7126 5 20 95 Section 5 Wiring Diagrams ADV5875 AB Figure 5 13 Reconnection Diagram ADV 5875...
Страница 96: ...TP 7126 5 20 96 Section 5 Wiring Diagrams Notes...
Страница 100: ...TP 7126 5 20 100 Appendix Notes...
Страница 101: ...TP 7126 5 20 101...
Страница 102: ...TP 7126 5 20 102...
Страница 103: ...TP 7126 5 20 103...