3.1 GENERAL
The
«
General
»
tab contains the parameters related to the presence message sending and the KNX bus
reset that can be initialized by communication object no.16. With use of the communication object no.37
«
Heartbeat
»
the device periodically sends out a telegram with
«
1
»
. With use of the communication object
no.36
«
Power supply is on
»
the device sends out a telegram with
«
1
»
a er a KNX bus reset, a device
startup and a short circuit. A er returning to normal working condition during the time delay no
telegrams are sent. Then, the
«
Power supply is on
»
telegram is the first one that is sent.
Figure 3.
General tab parameters
ETS Parameter
Setting
{Factory Default}
Comment
Heartbeat period [s]
10…32,000[s]
{60}
Info telegram (with
«
1
»
) is regularly sent a er this
time period
Induce a KNX bus reset
with 0; with 1; with 0 and 1
{
with 1
}
Set type of telegram to trigger (remotely) a KNX
bus reset
Delay time for
«
Power
supply on
»
(obj. 36)
disabled;
1min; 2min…5min; 10min;
15min…30min; 1h; 2h…8h
{
1min
}
When returning to normal operation, a er this
time delay, the info telegram (containing
«
1
»
) is
sent by CO no.36
Table 4.
General tab parameter settings
page 13