Name
Function
Description
Lenght
DPT
C
R
W
T
U
11
Telegram
traffic
threshold
Send
alarm
status
With the measured value
entering the threshold range a
telegram with value 0 or 1 is
sent. A er returning to normal
operating and passing
hysteresis a telegram with
value 0 or 1 is sent.
1 bit
X
X
X
12
Overload
number
Send
counter
value
With
«
Sending difference
»
and
«
Cyclic sending
»
the device
sends the number counter
value of overloads.
2 bytes
X
X
X
13
Overload
duration
Send
counter
value
With
«
Sending difference
»
the
device sends the time counter
value of overloads in s.
4 bytes
X
X
X
14
Short circuit
number
Send
counter
value
With
«
Sending difference
»
and
«
Cyclic sending
»
the device
sends the number counter
value of short circuits.
2 bytes
X
X
X
15
Load
detached
duration
Send
counter
value
When activated, the device
sends the time counter value
of load detachments (due to
short circuit, device startup
and KNX bus reset).
4 bytes
X
X
X
16
KNX bus reset
Initialize
Triggered by a telegram with
value 0 or 1, the device starts
a reset process.
1 bit
X
X
X
X
17
KNX bus reset
number
Send
counter
value
With
«
Cyclic sending
»
the
device sends the number
counter value of KNX bus
resets.
2 bytes
X
X
X
18
Total
operating
time
Send
counter
value
With
«
Sending difference
»
the
device sends the time counter
value of the total operating
time in s.
4 bytes
X
X
X
19
Operating
time since
startup
Send
counter
value
With
«
Sending difference
»
the
device sends the time counter
value of the time elapsed
since last device startup in s.
4 bytes
X
X
X
20
Startup
number
Send
counter
value
With
«
Cyclic sending
»
the
device sends the number
counter value of device
startups.
2 bytes
X
X
X
21
Duration 1
Send
counter
value
With
«
Sending difference
»
the
device sends the time counter
value (in s) of a pre-selected
variable (output current,
output voltage, temperature)
being in the threshold range.
4 bytes
X
X
X