4  COMMUNICATION OBJECTS

Name

Function

Description

Lenght

DPT

C

R

W

T

U

0

Output 
voltage

Send 
measured 
value

With 

«

Cyclic sending

»

 the 

device sends the measured 
output voltage value in V 
(or mV).

2 bytes
4 bytes

DPT9, 
DPT14

X

X

X

1

Output 
voltage 
threshold

Send 
alarm 
status

With the measured value 
entering the threshold range a 
telegram with value 0 or 1 is 
sent. A er returning to normal 
operating a telegram with 
value 0 or 1 is sent.

1 bit

X

X

X

2

Output 
current

Send 
measured 
value

With 

«

Sending difference

»

 and 

«

Cyclic sending

»

 the device 

sends the measured output 
current value in A (or mA).

2 bytes
4 bytes

DPT7, 
DPT9, 
DPT14

X

X

X

3

Output 
current 
threshold

Send 
alarm 
status

With the measured value 
entering the threshold range a 
telegram with value 0 or 1 is 
sent. A er returning to normal 
operating and passing 
hysteresis a telegram with 
value 0 or 1 is sent.

1 bit

X

X

X

4

Output 
current 
maximum

Send 
measured 
value

A er the expired tracking 
period with 

«

Automatic 

sending

»

 the device sends the 

measured output current 
value in A (or mA).

2 bytes
4 bytes

DPT7, 
DPT9, 
DPT14

X

X

X

5

Temperature

Send 
measured 
value

With 

«

Sending difference

»

 and 

«

Cyclic sending

»

 the device 

sends the measured 
temperature value in °C.

2 bytes

X

X

X

6

Temperature 
threshold

Send 
alarm 
status

With the measured value 
entering the threshold range a 
telegram with value 0 or 1 is 
sent. A er returning to normal 
operating and passing 
hysteresis a telegram with 
value 0 or 1 is sent.

1 bit

X

X

X

7

Temperature 
maximum

Send 
measured 
value

A er the expired tracking 
period with 

«

Automatic 

sending

»

 the device sends the 

measured temperature value 
in °C.

2 bytes

X

X

X

10

Telegram 
traffic

Send 
measured 
value

With 

«

Sending difference

»

 and 

«

Cyclic sending

»

 the device 

sends the measured bus load 
value in %.

1 byte

X

X

X

page 26

module-electronic.ru

Содержание Module PS-S.640.30.1

Страница 1: ...module electronic ru KNX POWER SUPPLY PS S 640 30 1 Application Program ver 1 0 User Manual ver 1 0 User Manual...

Страница 2: ...ter reset 8 2 3 Parameter structure for measurement sources 9 2 4 Programming 9 2 4 1 Programing button 9 2 4 2 Individual address assignment 10 2 5 KNX bus reset function 11 3 ETS database parameters...

Страница 3: ...in the KNX bus and protective against short circuit and overload Compact housing 2TE Additional output 29V DC Diagnostic function LED status indication Output current 640mA Leakage 5W Mains voltage 23...

Страница 4: ...x current total output 640mA 1 2A E iciency at nominal load 82 KNX interface Speci cation TP 256 Available application so ware ETS 4 and later KNX connector 4 wire EIB connector PUSH WIRE spring clips...

Страница 5: ...ge is 195 265V AC Red Input voltage is out of this range 2 Bus voltage VBUS Green KNX bus voltage 28 31V DC Red KNX bus voltage is out of this range 3 Telegram tra ic Green blinking Telegram tra ic 80...

Страница 6: ...y be carried out by quali ed personnel There is a risk of electric shock Be sure to turn o the power before installing or removing the device Even when the device is turned o the output terminals can...

Страница 7: ...a tracking period can be set At the end of every tracking period the maximum measured value can be sent on the bus or just be set as value of the appropriate object Four di erent Alarm tabs see chapt...

Страница 8: ...Counter Duration Counter Overload X X Short Circuit X Load Detached X KNX Bus Reset X Threshold Range X X Operating Time total since last startup X Device Startup X Table 1 Available event counters 2...

Страница 9: ...lic sending The actual value is periodically sent Threshold alarm Enables disables the threshold functionality and following options Threshold Crossing this limiting value executes the Behaviour on al...

Страница 10: ...atabase entry available for ETS4 and higher can be downloaded from the website and from the KNX Online Catalog With the ETS the Individual Address can be assigned to the device by setting the desired...

Страница 11: ...KNX Bus Reset is triggered a er a reset by button press and a er a reset by communication object A Device Startup takes place when there was a mains power outage or a er programming the device The nu...

Страница 12: ...ent and the temperature measurement can be activated The Maximum tracking tab contains the parameters for maximum current value and maximum temperature value detection within a Tracking Period In the...

Страница 13: ...tion during the time delay no telegrams are sent Then the Power supply is on telegram is the rst one that is sent Figure 3 General tab parameters ETS Parameter Setting Factory Default Comment Heartbea...

Страница 14: ...ed and located outside the working range 28 31V For example with no Output voltage hysteresis the Behaviour on alarm deactivation function is executed on just entering the working range The Output cur...

Страница 15: ...1 set value to 0 set value to 1 send value 0 Entering the working range Output current Output current mA disable enable disable Enable disable group associations measurement and following settings Obj...

Страница 16: ...able Enable disable the alarm function Threshold 0 110 C 70 Select threshold value to execute the Behaviour on alarm activation Hysteresis 1 40 C 1 Select hysteresis interval value to execute the Beha...

Страница 17: ...enable disable Enable disable group associations measurement and following settings Object type 2 byte DPT7 integer 2 byte DPT9 oat 4 byte DPT14 4 byte DPT14 Select datapoint type Automatic sending d...

Страница 18: ...erence 0 100 10 Di erence between actual and last sent value which triggers the sending Cyclic sending disabled 1min 2min 5min 10min 15min 30min 1h 2h 8h disabled Info telegram is sent regularly Alar...

Страница 19: ...t Behaviour on alarm deactivation disabled send value 0 send value 1 set value to 0 set value to 1 send value 0 Select action on leaving the threshold hysteresis range Table 7 Telegram tra ic tab para...

Страница 20: ...ror counters can be set to zero by writing a 1 to the communication object no 33 Counter reset Figure 9 Error counter tab parameters ETS Parameter Setting Factory Default Comment Overload number count...

Страница 21: ...r of short circuits disable enable disable Enable disable group associations number counter and following setting Sending di erence 0 500 0 disabled Di erence between actual and last sent value which...

Страница 22: ...ontaining the actual time counter value can be sent according to the pre set value di erence The operational counters can be set to zero by writing a 1 to the communication object no 33 Counter reset...

Страница 23: ...iations measurement and following setting Sending di erence 0 2 600 000 s 0 disabled 1 month 2 600 000s 1 day 86 000s Di erence between actual and last sent value which triggers the sending Operating...

Страница 24: ...ion 1 Duration 2 Duration 3 Duration 4 objects no 21 24 27 30 Figure 11 Alarm 1 tab parameters same applies to alarm 2 3 4 ETS Parameter Setting Factory Default Comment Alarm 1 disable enable disable...

Страница 25: ...sis range Duration 1 Sending di erence 0 2 600 000 s 0 disabled 1 month 2 600 000s 1 day 86 000s Info telegram is sent regularly when the time counter of threshold exceedance s reaches the pre set val...

Страница 26: ...and passing hysteresis a telegram with value 0 or 1 is sent 1 bit X X X 4 Output current maximum Send measured value A er the expired tracking period with Automatic sending the device sends the measur...

Страница 27: ...detachments due to short circuit device startup and KNX bus reset 4 bytes X X X 16 KNX bus reset Initialize Triggered by a telegram with value 0 or 1 the device starts a reset process 1 bit X X X X 1...

Страница 28: ...n s indicating the number of threshold events for output current output voltage temperature 2 bytes X X X 26 Threshold 2 Send alarm status With the measured value entering the threshold range a telegr...

Страница 29: ...ounter values and duration counter values except total operating time and device startup number are set to zero by a telegram with 1 1 bit X X X 34 Measured values Send all Measured values of output c...

Страница 30: ...5 STATE OF DELIVERY 5 1 DEFAULT FACTORY SETTING General Individual address 12 12 255 Heartbeat 60 s page 30 module electronic ru...

Отзывы: