3.5 ERROR COUNTERS
The
«
Error Counters
»
tab contains the menus
«
Overload number counter
»
,
«
Overload time counter
»
,
«
Short circuits number counter
»
and
«
Load detached time counter
»
. Activation of the parameters also
activates the related communication objects. Info telegrams containing actual values can be sent
regularly or according to a pre-set value difference. Error counters can be set to zero by writing a
«
1
»
to
the communication object no.33
«
Counter reset
»
.
Figure 9.
Error counter tab parameters
ETS Parameter
Setting
{Factory Default}
Comment
Overload number counter
Number of overloads
disable; enable
{
disable
}
Enable/disable group associations, number
counter and following settings
Sending difference
0…1,000
{
0
}
(= disabled)
Info telegram is sent regularly a er this number of
overloads
Cyclic sending
disabled;
1min; 2min…5min; 10min;
15min…30min; 1h; 2h…8h
{
disabled
}
Info telegram is sent regularly
page 20