3.3 MAXIMUM TRACKING
With setting the
«
Tracking period
»
a certain period of time is tracked in order to find the maximum
observed value contained. A er each expired period this value can be sent over the bus. The maximum
tracking function is available for the measurement sources
«
Output current
»
and
«
Device Temperature
»
.
Figure 5.
Maximum tracking tab parameters
ETS Parameter
Setting
{Factory Default}
Comment
Tracking period [s]
10…32,000[s]
{
1,800
}
Determination of the time period for maximum
value tracking
Maximum value of Output
current
Output current maximum
[mA]
disable; enable
{
disable
}
Enable/disable group associations, measurement
and following settings
Object type
2-byte(DPT7, integer);
2-byte (DPT9, float),
4-byte(DPT14)
{
4-byte(DPT14)
}
Select datapoint type
Automatic sending
do not send;
send at end of period
{
do not send
}
Info telegram containing the maximum measured
output current value is sent a er an expired
tracking period
Maximum value of Device
temperature
Device temperature
maximum [°C]
disable; enable
{
disable
}
Enable/disable group associations, measurement
and following setting
Automatic sending
do not send;
send at end of period
{
do not send
}
Info telegram containing the maximum measured
device temperature value is sent a er an expired
tracking period
Table 6.
Maximum tracking tab parameter settings