Safety Information
SensoGate® WA 131 H
Operation in Explosive Atmospheres
The SensoGate WA131H-X is certified for operation in explosive atmospheres.
• EU-Type Examination Certificate KEMA 04ATEX4035X
Exceeding the standard atmospheric conditions within the manufacturer’s specifications, such as ambient tem-
perature, process pressure and temperature, does not impair the durability of the retractable fittings.
Related certificates are included in the product’s scope of delivery and are available at www.knick.de in the cur-
rent version.
Observe all applicable local and national codes and standards for the installation of equipment in explosive at-
mospheres. For further guidance, consult the following:
• IEC 60079-14
• EU directives 2014/34/EU and 1999/92/EC (ATEX)
Possible Ignition Hazards During Installation and Maintenance
To avoid mechanically generated sparks, handle the SensoGate WA131H-X with care and apply suitable mea-
sures, e.g., use covers and pads.
The metallic parts of the SensoGate WA131H-X must be connected to the plant’s equipotential bonding using
the metallic process connection and the grounding connection provided for that purpose.
When components are replaced with genuine Knick spare parts made of other materials (e.g. O-rings), the infor-
mation given on the nameplate may deviate from the actual version of the SensoGate WA131H-X. The operating
company must assess and document this deviation.
Electrostatic charging
The drive unit of specific versions of the SensoGate WA131H-X contains housing components made of non-con-
ductive plastic. Due to their surface, the housing components may build up an electrostatic charge. To prevent
this charge from becoming an effective ignition source in Zone 0, ensure that the following conditions are met:
• Highly efficient charge generating mechanisms are excluded
• Non-metallic components are cleaned with a moist cloth only
Mechanically generated sparks
Single impacts on metal parts or collisions between metal parts of the SensoGate WA131H-X are not a potential
ignition source only if the following conditions are met:
• Possible impact velocity is less than 1 m/s
• Possible impact energy is less than 500 J
If these conditions cannot be ensured, the operating company must reassess single impacts on metal parts or
collisions between metal parts as potential sources of ignition. The operating company must implement suitable
risk minimization measures, e.g., by ensuring a non-explosive atmosphere.
Possible Ignition Hazards During Operation
When using non-water-based cleaning, rinsing, or calibration media with a low conductivity of less than 1 nS/m,
electrostatic charging of internal, conductive components may occur. The operating company must assess the
associated risks and implement appropriate measures.
The sensors that are used must be approved for operation in hazardous locations. Further information can be