NOTE: When connecting gas supply line, a
pressure test point must be installed downstream
from the shutoff valve for checking inlet gas
pressure.
5. The gas line to your laundry room should be
made of black iron pipe. A 3/8 inch pipe with an
inside diameter of 11.7 mm (0.46 inch) will be
adequate if length of supply line is not over 6 m
(20 feet). If length exceeds this, use 12.7 mm
(1/2 inch) pipe. If copper semi-rigid tubing is
used it must be internally tinned or equivalently
treated to resist sulfur corrosion.
NOTE: The dryer and its individual gas valve must
be disconnected from the gas supply piping system
during any pressure testing of that system at test
pressures in excess of 3.45 kPa (1/2 psig).
6. Check all pipe connections (internal and
external) for gas leaks with a soapy solution. Gas
connections should be checked annually for
leakage.
7. Be sure the shut off valve in your dryer is OPEN.
Your dryer is shipped with the valve open.
8. The dryer gas valve is equipped with a pressure
test point for checking manifold pressure.
For proper operation at altitudes above 760 m
(2500 feet) the gas valve spud orifice size must be
reduced to ensure complete combustion. Refer to
Step 5: Connect Dryer Exhaust System
•
DO NOT use plastic or thin foil ducting. Rigid
metal duct is recommended. Refer to
Natural Gas Altitude Adjustments
Altitude
Orifice Size
Part
Number
m
ft
No.
mm
inches
760
2500
45
2.08
0.0820
503779
1370
4500
46
2.06
0.0810
503780
1830
6000
47
1.99
0.0785
503781
2290
7500
48
1.93
0.0760
503782
2900
9500
49
1.85
0.0730
503783
3355
11,000
50
1.78
0.0700
503784
Table 1
LP Altitude Adjustments
Altitude
Orifice Size
Part
Number
m
ft
No.
mm
inches
1370
4500
56
1.2
0.0465
503786
3000
9500
57
1.1
0.043
60941
Table 2
SWD449N
Figure 9
To reduce the risk of fire and combustion
gas accumulation the dryer MUST be
exhausted to the outdoors.
W604
To reduce the risk of fire and the
accumulation of combustion gases, DO NOT
exhaust dryer air into a window well, gas
vent, chimney or enclosed, unventilated
area, such as an attic, wall, ceiling, crawl
space under a building or concealed space
of a building.
W045
WARNING
This gas appliance contains or produces a
chemical or chemicals which can cause
death or serious illness and which are
known to the State of California to cause
cancer, birth defects, or other reproductive
harm. To reduce the risk from substances in
the fuel or from fuel combustion, make sure
this appliance is installed, operated, and
maintained according to the instructions in
this manual.
W115
To reduce the risk of fire, DO NOT use
plastic or thin foil ducting to exhaust the
dryer.
W354
WARNING
SWD449N
DO
DON’T