Connecting temperature sensors
The regulator cooperates with sensors of the
CT4 type. The use of other types of sensors
is prohibited.
The sensor cables may be extended with
cables with a cross-section of not less than
0.5 mm2. The total length of each sensor
cable should not exceed 15 m, however.
Sensor cables should be separated from
mains cables. Otherwise, the temperature
may not be displayed correctly. The
minimum distance between these wires
should be 100 mm.
The internal temperature sensor, type CT4,
should be installed inside the room, marked
as the 1st heating zone. Recommended
installation above the heater, usually 100…
200 mm from the point on the ceiling that
marks the center of the heater.
Do not install the internal
temperature sensor closer than
1000 mm from the air outlet to
the room, so as not to cause its
heating
and
erroneous
temperature measurement.
Good thermal contact between the sensors
and the measured surface should be
ensured. It is not allowed to flood the
sensors with oil or water. The sensors must
also be secured against loosening from the
surfaces to which they are attached. Do not
allow sensor cables to come into contact with
hot elements of the furnace. Temperature
sensor cables are resistant to temperature
not exceeding 100 ° C..
5.4
Connecting weather sensor
The regulator cooperates only with a weather
sensor of the CT6-P type. The sensor should
be installed on the coldest wall of the
building, usually it is the northern side, in a
roofed place. The sensor should not be
exposed to direct sunlight and rain. Install
the sensor at a height of at least 2 m above
the ground, away from windows, chimneys
and other heat sources that may interfere
with the temperature measurement (at least
1.5 m). Use a wire with a cross-section of at
least 0.5 mm2 and a length of up to 25 m for
the connection. The polarity of the wires is
not important. Connect the other end to the
regulator terminals. The sensor should be
screwed to the wall with mounting screws.
Access to the holes for mounting screws is
obtained after unscrewing the cover of the
sensor housing.
It is possible to additionally adjust the
weather sensor indications. To do this,
measure
the
value
of
the
outside
temperature with a thermometer and enter
the obtained value of the temperature
difference between the measured and
indicated by the weather sensor in the menu:
Main settings - Sensor correctionPodłączenie
czujnika temperatury spalin
The regulator cooperates with a CT2S
sensor. The use of any other type of sensor
is prohibited.The flue gas temperature sensor
should be installed in the stove's flue. The
gap between the sensor and the flue should
be sealed. The sensor should be installed by
a qualified installer, in accordance with the
regulations for chimney installations. The flue
gas sensor cable must not touch the hot
elements of the stove and the flue. The
sensor should be installed at such a distance
from the burner that it will not be exposed
directly to the flames of the burner fire and
the temperature of the exhaust gases doe
Содержание ecoMAX920 P1-CH
Страница 6: ...Manual ecoMAX920P1 CH...
Страница 14: ...14 ecoNET app...
Страница 15: ...15...
Страница 16: ...16 INSTALLATION MANUAL AND SERVICE SETTINGS ecoMAX920P1 CH...
Страница 33: ...33...
Страница 34: ...34 ul Obornicka 71 62 002 Suchy Las Polska Tel 61 811 70 37 biuro kipi pl www kipi pl BDO 000179569...