3.3

 

Mode OPERATION 

In  the  OPERATION  mode,  the  burner  fan 
operates  continuously,  the  fuel  feeder  is 
activated  cyclically,  where  the  cycle  consists 
of  the  feeder  operation  time  and  the  fuel 
feeding 

pause 

time.

 

Burner and feeder fan cycles. 

 

The Cycle time parameter in the OPERATION 
mode is available in the menu: 

Service settings 

 Burner settings 

 

Operation 

The operation time of the fuel feeder is 
calculated automatically depending on the 
required current power of the furnace, feeder 
efficiency and fuel calorific value. The power 
parameters of the burner blower fan for 
individual stove power levels are available in 
the menu: 

Oven settings 

 Power modulation 

 

Regulation modes 

You  can  choose  between  two  control  modes 
responsible 

for 

stabilizing 

the 

set 

temperature  of  the  airflow:  Standard  and 
Fuzzy Logic. The mode changes in the menu: 
Oven settings 

 Regulation mode  

 

• Working in Standard Mode 

If  the  airflow  temperature  reaches  the  set 
value,  the  regulator  will  switch  to  the 
SUPERVISION mode. 
The  controller  has  a  burner  power 
modulation  mechanism  that  allows  to 
gradually  reduce  its  output  as  the  heat 
exchanger  (supply)  temperature  approaches 
the set value. Three burner power levels are 
defined: 

maximum, 

intermediate 

and 

minimum.  Each  level  can  be  assigned  a 
separate  burner  blower  fan  power,  which 
translates into the actual burner power level. 

The  parameters  of  the  burner  power  levels 
are available in the menu: 
Furnance settings 

 Power modulation 

The controller decides about the power of the 
burner  with  which  the  furnace  will  work  at 
the  moment,  depending  on  the  set 
temperature  of  the  airflow  and  defined 
hysteresis:  Intermediate  power  -  H2 
hysteresis  and  Minimum  power  -  H1 
hysteresis. It is possible to configure the H1 
and  H2  hysteresis  values  so  that  the 
modulation  will  take  place  without  an 
intermediate  state,  i.e.  transition  from  Max. 
To Min. Without the Intermediate power. 
 

 

Power modulation hysteresis.

 

 

• Operation in Fuzzy Logic mode 

In the Fuzzy Logic mode, the controller 
automatically determines the power of the 
burner with which the furnace will operate so 
as to maintain the airflow temperature at the 
set level. The controller uses the same 
defined burner power levels as in Standard 
mode. For this mode, it is not necessary to 
set parameters: Maximum power - H2 
hysteresis and Minimum power - H1 
hysteresis. The Fuzzy Logic mode, unlike the 
Standard mode, does not have the 
disadvantage in which the preset airflow 
temperature will not be reached due to 
incorrect selection of hysteresis H2, H1. 
Moreover, it enables faster reaching the set 
temperature. Additionally, the burner power 
range can be set using the parameters 
Minimum boiler output FL and Maximum 
boiler output FL. 

After exceeding the preset airflow 
temperature by 5ºC, the regulator switches 
to the SUPERVISION mode. 

Содержание ecoMAX920 P1-CH

Страница 1: ...coMAX920P1 CH FOR BLOWING TYPE BOILER FOR SOLID FUEL I OPERATING AND INSTALLATION MANUAL ISSUE 1 0 09 2020 the device is not a standard equipment of the regulator ecoNET300 ecoNET apk ecoNET app www e...

Страница 2: ...ction of the wires may damage the regulator The controller cannot be used in conditions of water vapor condensation and exposed to water MAIN PRINCIPLES OF PROPER FUZZY LOGIC FURNISHING The controller...

Страница 3: ...MENTS 12 3 INSTALLATION OF THE CONTROL PANEL 12 4 WORKING MODULE INSTALLATION 12 5 IP PROTECTION RATE 12 6 ELECTRICAL CONNECTION 19 12 7 ELECTRICAL SCHEME 22 12 8 CONNECTION OF TEMPERATURE SENSORS 12...

Страница 4: ...rinsically safe device ie in a failure condition it can be a source of a spark or high temperature which in the presence of flammable dusts or gases may cause a fire or explosion The surroundings of t...

Страница 5: ...ept no liability for damage caused by failure to follow the instructions 4 Record keeping Please keep this installation and operating manual and all other applicable documentation carefully so that yo...

Страница 6: ...Manual ecoMAX920P1 CH...

Страница 7: ...FL Feeder Feeder efficiency Feeder efficiency time Efficiency feeder time Fuel weight Filling the feeder Regulation mode Standard Fuzzy Logic Fuel Level Alarm level Fuel Level calibration Cleaning Bur...

Страница 8: ...econd method to turn on the stove Press the menu button and then press the button To turn off the stove press the menu button and then press button then the stove will go into the extinguishing proces...

Страница 9: ...which translates into the actual burner power level The parameters of the burner power levels are available in the menu Furnance settings Power modulation The controller decides about the power of th...

Страница 10: ...this will increase the temperature of the burner The parameters of the SUPERVISION mode must be selected so that the burner temperature in this mode gradually drops Incorrect settings can lead to over...

Страница 11: ...ature Thanks to this when selecting a heating curve appropriate for a given building the room temperature heating zone will remain approximately constant regardless of the outside temperature Heating...

Страница 12: ...ek in the Schedule setting Fuel level configuration Activation of the fuel level indicator To enable display of the fuel level set the parameter value Stove settings Fuel level Alarm level to a value...

Страница 13: ...nd from the next room panel it closes the SP2 damper and then another SP3 damper If all the room panels report no heat demand in all heating zones the stove switches to the BURNING OFF mode and then t...

Страница 14: ...14 ecoNET app...

Страница 15: ...15...

Страница 16: ...16 INSTALLATION MANUAL AND SERVICE SETTINGS ecoMAX920P1 CH...

Страница 17: ...temperature sensor 5 supply temperature sensor 6 exhaust fan 7 burner fan and burner feeder 8 air damper actuator 9 room panel with a room thermostat function 10 external air intake 11 air supply duc...

Страница 18: ...ions of wheel transport IP protection class The casing of the regulator provides IP20 protection The casing on the side of the terminal cover has the IP00 protection degree therefore the terminals mus...

Страница 19: ...onnected to it You should remember about the safety rules related to electric shock The regulator must be equipped with a set of plugs inserted into the connectors for supplying 230V devices With a me...

Страница 20: ...d cable 5 cable clamp 6 connector Separate electrical wiring from hot stove components especially flue pipes After connecting the wires it is absolutely necessary to put the cover back in its place Al...

Страница 21: ...stat function HS heater exchanger temperature sensor CT4 ES type supply temperature sensor type CT4 FS exhaust gas temperature sensor type CT2 S FOS feeder temperature sensor type CT4 T thermostat int...

Страница 22: ...all of the building usually it is the northern side in a roofed place The sensor should not be exposed to direct sunlight and rain Install the sensor at a height of at least 2 m above the ground away...

Страница 23: ...T6 P weather External Temp C Min Nom Max 25 901 6 901 9 902 2 20 921 3 921 6 921 9 10 960 6 960 9 961 2 0 999 7 1000 0 1000 3 25 1096 9 1097 3 1097 7 50 1193 4 1194 0 1194 6 100 1384 2 1385 0 1385 8 1...

Страница 24: ...iler it will supply 12V DC to terminals 43 44 After the furnace temperature drops below the parameter Reserve boiler activation temperature the regulator will stop supplying voltage to contacts 43 44...

Страница 25: ...vice The safety temperature limiter must have a rated operating voltage of at least 230 V and should have the applicable approvals Dangerous voltage is present on terminals 1 2 If the STB is not insta...

Страница 26: ...eration detection Fan speed multipier Burning off Max time of burning off Min time of burning off Blowing power Blowing time Blowing pause Blowing start Blowing stop Cleaning Cleaning time firing up C...

Страница 27: ...eration time with minimum power after firing up The power is determined by the parameter Minimum power airflow job Thermostat mode Switches the burner into Thermostat mode where the burner works with...

Страница 28: ...llows you to burn the fuel supplied in Supervision with low emissions Minimum blowing power Minimal power of the burner blower fan that can be selected by the user of the regulator It is only used to...

Страница 29: ...rs Log out Restoring the service settings will also restore the settings from the main user menu Exit H Selecting Yes saves all service settings after changing parameters in the service menu Touch pan...

Страница 30: ...ering up the regulator Checking the temperature sensor is described in point 12 11 6 4 Unsuccessful firing up attempt The alarm will occur after the third unsuccessful attempt to automatically fire up...

Страница 31: ...nents 7 2 Replacing the mains fuse The mains fuse is located inside the controller housing The fuse may only be replaced by a suitably qualified person after disconnecting the mains supply Use time de...

Страница 32: ...manually the limiter should be unlocked point Check the burner fan and replace if necessary The exhaust fan is not working Check if the mains fuse of the exhaust fan is not blown and replace if neces...

Страница 33: ...33...

Страница 34: ...34 ul Obornicka 71 62 002 Suchy Las Polska Tel 61 811 70 37 biuro kipi pl www kipi pl BDO 000179569...

Отзывы: