1011026 User Manual Issue 01 (26.10.2021) 

 

 

1.

 

Health and Safety 

These warnings are provided in the interest of safety. You must read them carefully before installing or using 
the equipment. 
It is important that this document is retained with the equipment for future reference. Should the equipment 
be transferred to a new owner, always ensure that all relevant documents are supplied in order that the new 
owner can become acquainted with the functioning of the equipment and the relevant warnings.  
To ensure that the equipment described is safe both for personnel and property it should be installed, 
inspected, and maintained by or under the supervision of qualified persons (Electrician)   
Covers must be kept locked. Observe all hazard labels and take appropriate action to avoid exposure to the 
risks indicated. Ensure that you are familiar with the safe working areas and accesses. Ensure that the working 
area is adequately lit.  
The power supply to the equipment should be isolated at the main RCD before lifting the blower cover.   
Take care to maintain correct posture, particularly when lifting. Use appropriate lifting equipment when 
necessary. Always keep proper footing and balance. Avoid any sharp edges.  

 

Health & Safety at Work, etc. ACT 1974  

Regard should be taken of IEE Wiring Regulations, Codes of Practice, Statutory Requirements, and any specific 
instructions issued by the supplier of these details.    
Earthing - All equipment must be earth bonded in accordance with the latest IEE Wiring Regulations.  For 
clarity this has not been shown.  
We reserve the right to alter these details without prior notice.  

2.

 

Declaration of Conformity 

This product meets all the essential safety requirements of the relevant European Directives. 
The full text of the Declaration of Conformity can be provided upon request. 

3.

 

General Description 

The DTP control Panel is used to control and monitor the Kingspan Klargester Domestic Wastewater Treatment 
Units. It is capable of operating multiple pump/motor outputs at set times in accordance with pre-determined 
timetables.  

4.

 

General Operation 

The control unit continuously monitors the internal timetables and operates the appropriate pump/motor 
outputs  according to a timetable entry. The status is  shown on the display. The current time continues to be 
updated internally by battery backup when the mains fail, and the control unit continues normally upon mains 
being restored. 

5.

 

Applicable Firmware 

The operation described in this manual refers to control units with the following firmware: 

Firmware ID 

Description 

Version 

FMW-1112 

Kingspan 1002510 

RV1.22 

6.

 

Technical Support 

Technical support & 

PIN

 may be obtained from: 

Kingspan Water & Energy 

 Service 

College Road, 
Aylesbury 
HP22 5EW 

Phone UK: 03332406868 
Phone ROI: 04838362400 
Or 
Contact Kingspan Area Sales Manager 

Содержание Klargester 1002510

Страница 1: ...Kingspan Klargester 1011026 Domestic Wastewater Control Panel USER MANUAL...

Страница 2: ...Installation of High Level Alarm HLA where applicable 6 Beacon units P No 1009254 where applicable 7 Installation of High Level Alarm HLA where applicable 7 For Biotec Bioficient or BioSafe Applicati...

Страница 3: ...of Practice Statutory Requirements and any specific instructions issued by the supplier of these details Earthing All equipment must be earth bonded in accordance with the latest IEE Wiring Regulation...

Страница 4: ...1011026 User Manual Issue 01 26 10 2021 4 7 Installation Figure 1 1002510 Lid Cover Figure 2 Enclosure Mounting Dimensions Figure 3 Control Panel Wiring 1...

Страница 5: ...1011026 User Manual Issue 01 26 10 2021 5 Figure 4 DTP Control Panel Wiring 2...

Страница 6: ...tape at a depth of 150mm For loads up to 0 75kW and runs of less than 100 metres 2 5mm 3 core SWA is adequate For loads up to 1 55kW and runs of less than 100 metres 4 0mm 3 core SWA should be used I...

Страница 7: ...Applications 7 7 1 Power Pressure Failure Detection System PPFDS where applicable The panel is designed to be used in conjunction with the Beacon unit to provide warning of either loss of power or ai...

Страница 8: ...te socket below the battery on the PCB marked J3 After finishing wiring replace the isolator cover and screw Turn the mains supply on at the source Turn on the panel using the isolation switch It shou...

Страница 9: ...vation time Alarms The conditions shown below cause an alarm message to appear on the display the beeper sounds the beacon flashes and the common alarm telemetry relay is de energised Some alarm condi...

Страница 10: ...factory defaults This menu is intended for use by installation Service engineers only The menu is entered by simultaneously pressing then releasing the three buttons On entry to the menu all outputs...

Страница 11: ...4 hour format The display will show Figure 13 Date Time Use and to move between date and time Pressing the button will freeze display of the clock and enter edit mode to allow the date or time to be s...

Страница 12: ...ickle Charge indicates that the unit is fully charged and maintaining the battery 8 6 7 Factory Defaults This option allows the control unit to be set back to the defaults as they were when the unit l...

Страница 13: ...lower J9 Chemical dosing pump Grundfos KP 350 Grundfos KP 250 Secoh JDK 250 Kingspan 404390 Fusing F1 De sludge pump terminals 3 4 T 5A H 250V F2 Internal power supply unit T 2A H 250V F3 Motor blower...

Страница 14: ...y 16 x 2 character LCD Green power LED Real Time Clock Event log timestamps and controlling the operation of the motors blowers according to a timetable LED Beacon 1009254 Only the LED beacon 1009254...

Страница 15: ...ay Motor Blower Start Time Time of Day where Unit is started 00 00 00 Stop Time Time of Day where Unit is stopped 23 59 59 Run Time Time for the components to Run 23 59 59 24 hours Pause Time Time for...

Страница 16: ...1011026 User Manual Issue 01 26 10 2021 16 This Page Intentionally Left Blank...

Отзывы: