ZCVRB60 -Clearance to Combustibles –Vented Chase
-Ventilation Plates Removed-
Clearance to Combustibles ZCVRB60 Vented Chase
Front
36” [92cm]
Back (from Stand-offs)
0” [0cm]
Side (from Stand-offs)
0” [0cm]
Floor
0” [0cm]
Minimum Ceiling Height (from bottom of fireplace) 76” [193cm]
Top (from Stand-offs)
0” [0cm]
Top of 90° Bend in minimum Enclosure of 76”
4” [10.2cm]
Top of 90° Bend in Enclosure over 76”
4” [10.2cm]
VENTING SYSTEMS
Top of Horizontal Pipe
2” [5cm]
Side & Bottom of Horizontal Pipe
1” [2.5cm] All Vent Systems
Vertical Vent Pipe
1” [2.5cm] All Vent Systems
REFER TO FACING REQUIREMENTS SECTION FOR FACING MATERIALS
Sealed Enclosure Top
⚠
NOTE:
If using insulation in vented chase (i.e. for outside wall), wall board / drywall is required to support all insulation.
Vented chase must be clean and free of all debris (i.e. loose insulation, pieces of wood, etc.).
⚠
NOTE:
HEAT CANNOT BE DISCHARGED INTO THE WALLS, FLOOR, OR CEILING.
Heat must exit through the required
vented chase opening near the ceiling.
Sealed Enclosure Top
MIN 200 Square inch opening
must be within 3/4” of the
Sealed Enclosure Top.
VL60EG Shown
MIN
MIN