ZCVRB60 – Vented Chase – Style 1 – OPENING WITH NO GRILL
VENTILATION PLATES MUST BE
REMOVED.
Minimum Enclosure Height is 76” from
the bottom of the appliance.
For vertical venting use a Firestop
(Z58FS) or Attic Insulation (Z58AIS,
Z58AIS24) Shield through enclosure top.
MINIMUM CHASE OPENING IS 200
SQUARE INCHES FREE AIR.
⚠
NOTE:
HEAT CANNOT BE DISCHARGED INTO THE WALLS, FLOOR, OR
CEILING.
Heat must exit through the required vented chase opening near
the ceiling.
ELECTRICAL WIRES IN CHASE MUST BE PROPERLY ATTACHED
TO INSIDE WALL OF CHASE. DO NOT RUN WIRES ABOVE THE
APPLIANCE.
Please follow the current CSA C22.1 Canadian Electrical Code or the
National Electrical Code; ANSI/NFPA 70 when installed in the United
States.
If using insulation in vented chase (i.e. for outside wall), wall board / drywall is required to support all insulation.
Vented chase must be clean and free of all debris (i.e. loose insulation, pieces of wood, etc.)
FRAMING TO CEILING-
OPEN FRONT
NO GRILL
Finished Minimum
Opening is
200 square
inches
of free air.
-OPEN CHASE
FRAMING-
ENCLOSURE MIN
1-7/8” BELOW
CEILING
Finished Minimum
Opening is
200
square inches
of
free air.
Requires 1-7/8”
Minimum Opening
below Ceiling
Opening
directly below
Enclosure
Top / Ceiling
FRAMING TO CEILING-
OPEN SIDES
NO GRILLS
Finished Minimum
Opening is
200 square
inches
of free air.
NOTE:
Sides of
enclosure must have
equal sized openings.
Openings are
directly below
Enclosure
Top / Ceiling
Openings are
directly below
Enclosure
Top / Ceiling
FRAMING TO
CEILING- OPEN
FRONT AND BACK
NO GRILL
Each opening must be
200 square inches
of
free air.
Both Chase Vent
Openings Must be in
the same Pressure
Zone
(Room / Area)
70”
MIN
19-1/4”
MIN
20