ZCVRB60 – Vented Chase – Style 2 – OPENING WITH GRILL
VENTILATION PLATES MUST BE REMOVED.
Grill openings must be within 3/4” of enclosure top.
Minimum Enclosure Height is 76” from the bottom of
the appliance.
For vertical venting use a Firestop (Z58FS) or Attic
Insulation (Z58AIS, Z58AIS24) Shield through
enclosure top.
If
Kingsman VL60EG
Grill is used,
minimum rough
opening required is 3-5/8” x 60-5/8”.
Any obstacles,
such as vertical studs should be notched back 1-1/2”
from finished face of wall.
⚠
NOTE: HEAT CANNOT BE DISCHARGED INTO THE
WALLS, FLOOR, OR CEILING.
Heat must exit through the
required vented chase opening near the ceiling.
ELECTRICAL WIRES IN CHASE MUST BE PROPERLY
ATTACHED TO INSIDE WALL OF CHASE. DO NOT RUN
WIRES ABOVE THE APPLIANCE.
Please follow the current CSA C22.1 Canadian Electrical
Code or the National Electrical Code; ANSI/NFPA 70 when
installed in the United States.
⚠
NOTE:
Outsourced grills must have
220 square inches
minimum free air opening and no sloping louvers
If using insulation in vented chase (i.e. for outside wall), wall board / drywall is required to support all insulation.
Vented chase must be clean and free of all debris (i.e. loose insulation, pieces of wood, etc.)
FRAMING TO CEILING-
GRILL AT FRONT
Grill must have a total of
220
square inches
free air
minimum.
FRAMING TO CEILING-
GRILLS AT FRONT
AND BACK
Each grill must be
220
square inches
free air
minimum.
Both Chase Vent
Openings Must be in
the same Pressure
Zone (Room / Area)
2”
MAX
Grill Opening must be within
3/4” of Enclosure Top
Grill Opening must be
within 3/4” of Enclosure
Top
Grill
Opening
must be
within 3/4”
of Enclosure
Top
FRAMING TO
CEILING-
SIDE GRILLS
Grills must have a
total of
220 square
inches
free air
minimum.
NOTE:
Sides of
enclosure must have
equal sized grills.
FRAMING TO CEILING- MINIMUM
ENCLOSURE- GRILL AT FRONT
Grill must have a total of
220
square inches
free air minimum.
Grill Opening must be within
3/4” of Enclosure Top
(Continued on next page)
76”
MIN
22