Venting Straight Up Through Roof 

An Attic Insulation Shield must be installed where the vent passes from a lower living space into an attic space where the chimney is 

not enclosed. It is designed to keep insulation materials away from the chimney. 

When installing the Attic Insulation Shield where the chimney passes from a living space to an attic space, install the shield from below 

and nail in place using 1" spiral nails. 

A fire stop must be installed on the bottom side of the joists when passing through a ceiling or floor. If an attic insulation shield is to be 

used, a fire stop is not required. 

   

 

 

 

 

Using Flex Bends 

Avoid cutting joists by offsetting the flex pipe.  

When using 45° bends a bend support is required directly above the highest bend. 

When installing a bend in a joist area a minimum of 4" clearance to combustible to the top of bend must be maintained, sides and 

bottom of pipe, a 1" clearance to combustibles must be maintained. If running horizontal through an area a 1-1/2" minimum clearance to 

the top of the horizontal pipe must be maintained. 

Maximum vertical height of system should not exceed 43 feet. 

Use roof support and rigid pipe at roof level. Flex pipe is not permitted within roof support. 

When penetrating the roof a rigid galvanized pipe must be used. Attach flex pipe to the rigid pipe with high temperature sealant, secure 

with four screws assuring the flex pipe and rigid pipe are secured. Attach rigid pipe to termination with sealant and screw with 4 sheet 

metal screws. The Inner flex pipe must be secured with 4 screws which must penetrate both the flex pipe and inner section of 

termination.

 

Attach 7” rigid pipe to 7” termination with sealant and screw with 4 sheet metal screws. 

Vertical termination clearance is 18" [45.7cm] above the roof, measured from highest point of exit on the roof line. 

Support vertical pipes to maintain minimum of one inch or greater clearances to combustibles. 

Roof Flashing 

Ensure that you have the proper roof flashing by checking your roof pitch using a level and two rulers, or by using a roof pitch card. 

Slide a Roof Flashing suitable to your roof slope over the vent. Place the edge of the flashing plate that will be on the higher part of the 

roof slope under the shingles. Both the sides and the lower edge lay on top of the shingles. 

NOTE: At the top edge of the flashing plate, lift the shingles and nail the plate to the roof deck, then cement the shingles to 

the plate with a suitable waterproof mastic. 

Ensure that the chimney is plumb. Square up the flashing plate and nail in place to the roof deck. Use 12 nails with neoprene washers 

or cover the heads with a suitable waterproof mastic. Wrap the storm collar around the vent above the flashing. Secure the ends 

together loosely with nut and bolt supplied. Slide the collar down the vent until it comes in contact with the flashing. Tighten the bolt and 

seal the Storm Collar to the vent with a suitable waterproof non-combustible mastic. 

The flashing and storm collar should be painted to match the roof shingles. This will extend its life and improve the appearance. Clean, 

prime and paint with suitable painting products. 

Vertical Venting in Cold Climates 

In cold climate conditions where temperatures go below -10 degrees Celsius or 14 degrees Fahrenheit, we recommend that the chase 

be insulated and where the vent pipe enters into the attic space that the pipe be wrapped with an insulated Mylar sleeve. This will 

increase the temperature of the vent and help the appliance to vent properly in cold weather conditions. 

It is also important in vertical vented direct vent appliances that the appliance be operated daily during the winter months as this will 

help stop the termination from freezing up.  

 

We recommend using a thermostat set at room temperature to allow the unit to cycle.

 

For IPI models it may be necessary to set the appliance to Standing Pilot mode to maintain heat in the cavity. The purpose of this 

procedure is to prevent cold air from penetrating the chimney and then onto the living space. Therefore, when the internal temperature 

is slightly elevated the fireplace is able to freely exhaust its combustion and hence making it easier to start up. 

 

 

 

-ALSO SEE DIAGRAMS ON FOLLOWING PAGE-

 

 

Attic Insulation Shield 

Fire Stop 

 

75

Содержание HBZDV4736

Страница 1: ...sion of R Co Inc 2340 Logan Avenue Winnipeg Manitoba Canada R2R 2V3 Ph 204 632 1962 Printed in Canada February 9 2021 Part 36MQ MAN17 INSTALLER Leave this manual with the appliance CONSUMER Retain thi...

Страница 2: ...sman Fireplace Venting Parts 27 COMMON SECTION Clearances Mantels 28 Mantel Leg Clearances 29 Fan Installation 30 Split Receptacle Fan Speed Control Outside of Fireplace 31 Installing MQRB4236T Liner...

Страница 3: ...ame Control Room Thermostat 67 Smart Thermostat Fan Speed Control Light Control 68 Label Schematic 69 VENTING SECTION Vent Terminal Clearances 70 General Vent Installation Information 71 Installation...

Страница 4: ...sounds produced by a furnace or heating duct This noise does not affect the operation or longevity of your fireplace It is also normal for the fan to make some noise when it comes on This noise can be...

Страница 5: ...until unit is COMPLETELY cool before touching glass or attempting to install or remove Child Safety Screens To install screens hook bottom clip onto glass door frame then press down and push upper cli...

Страница 6: ...SI Z21 88 IN THIS MANUAL MAY BE INSTALLED IN MANUFACTURED MOBILE HOMES IN CANADA Please follow the current ANSI NFPA 70 National Electrical Code in the USA and CAN CSA C22 1 Canadian National Electric...

Страница 7: ...due to excessive lint from carpeting bedding material et cetera It is imperative that control compartments burners and circulating air passageways of the appliance be kept clean Make sure that the ga...

Страница 8: ...ication plate shall be mounted at the exterior of the building four feet directly above the location of vent terminal The plate shall be of sufficient size to be easily read from a distance of eight f...

Страница 9: ...mal shock Take care to prevent water from contacting the fireplace especially if it is hot See Through Units are suitable for an outdoor location but not on the outside wall of a house or other struct...

Страница 10: ...on Wall Corner F Exterior Wall See Mantel Leg Clearances Instruction for the proper placement of fireplace Island installation with a top vent is possible as long as the horizontal portion of the vent...

Страница 11: ...e the elbow on any horizontal runs of one foot or greater This allows for cleaner combustion and greatly reduces carboning and cleaning of glass MQHBZDV3636 Framing for your Gas Fireplace MQHBZDV36 Lo...

Страница 12: ...HBZDV36 WITH HB36CVCK CLEAN VIEW CIRCULATING KIT HBZDV36 Framing and Facing Requirements Non Combustible Header Attached AA Non Combustible Header Attached AA AA AA AA 12...

Страница 13: ...fireplace 60 inches 150 cm Top from standoffs 0 inches 0 mm Top of 90 degree bend in Minimum Enclosure of 42 to 43 inches 3 1 2 inches 89 mm All Vent Systems Top of 90 degree bend in Enclosure over 43...

Страница 14: ...T 1001 P165SI Orifice Pilot NG 977 165 TC SIT 1001 P167SI Orifice Pilot LP 977 167 TC SIT 1001 P633SI Valve Nova LP Hi Lo 0820651 1001 P634SI Valve Nova NG Hi Lo 0820652 1001 P713SI Pilot Burner LP 19...

Страница 15: ...hield Large Return Z47GP36 Galvanized Pipe 7 Dia x 36 Vertical Installations ZDVAAF Flashing 7 c w Storm Collar 1 12 to 7 12 ZDVAF2 Flashing 7 c w Storm Collar 8 12 to 12 12 ZDVAF3 Flashing 7 c w Stor...

Страница 16: ...on Wall Corner F Exterior Wall See Mantel Leg Clearances Instruction for the proper placement of fireplace Island installation with a top vent is possible as long as the horizontal portion of the vent...

Страница 17: ...of two and a half 2 5 inches above the bend in enclosures 5 For a fireplace with louvers combustible floor can raise 1 above the bottom of the fireplace For a fireplace with HB42CVCK Clean view Circu...

Страница 18: ...HBZDV42 WITH HB42CVCK CLEAN VIEW CIRCULATING KIT HB42 Framing and Facing Requirements Non Combustible Header Attached Non Combustible Header Attached 18...

Страница 19: ...om of fireplace 60 inches 150 cm Top from standoffs 0 inches 0 mm Top of 90 degree bend in Minimum Enclosure of 45 to 46 inches 5 inches 128 mm All Vent Systems Top of 90 degree bend in Enclosure over...

Страница 20: ...sembly Natural Gas c w Valve System MQRB4236NT 4236RBT BLPSI Burner Assembly Liquid Propane c w Valve System MQRB4236LPT Conversion Kit Sit Valve Only 4232HB CKLP MQHBZDV4236LP Millivolt 4232HB CKLPI...

Страница 21: ...Termination converts from 15 40 to under 15 FDVHT Horizontal Vent Termination FDVHSQ Horizontal Square Termination Z47ST24 Horizontal Snorkel Termination 24 Z47ST36 Horizontal Snorkel Termination 36...

Страница 22: ...on Wall Corner F Exterior Wall See Mantel Leg Clearances Instruction for the proper placement of fireplace Island installation with a top vent is possible as long as the horizontal portion of the vent...

Страница 23: ...nsulation sleeve is not required 5 For a fireplace with louvers combustible floor can raise 1 above the bottom of the fireplace For a fireplace with HB47CVCK Clean view Circulating Kit floor or hearth...

Страница 24: ...Non Combustible Header Attached Non Combustible Header Attached 24...

Страница 25: ...p of 90 degree bend in Minimum with insulation sleeve Enclosure of 50 1 2 to 56 1 2 inches 2 1 2 inches 64 mm All Vent Systems Top of 90 degree bend in without insulation sleeve Enclosure over 56 1 2...

Страница 26: ...1001 P633SI Valve Nova LP Hi Lo 0820651 1001 P634SI Valve Nova NG Hi Lo 0820652 1001 P713SI Pilot Burner LP 199 713 TC SIT 1001 P714SI Pilot Burner NG 199 714 TC SIT Optional Thermostats and Remote C...

Страница 27: ...hield Large Return Z47GP36 Galvanized Pipe 7 Dia x 36 Vertical Installations ZDVAAF Flashing 7 c w Storm Collar 1 12 to 7 12 ZDVAF2 Flashing 7 c w Storm Collar 8 12 to 12 12 ZDVAF3 Flashing 7 c w Stor...

Страница 28: ...s HB36 HB42 HB47 Mantels Warning Combustible objects must not be placed on a non combustible mantel unless the non combustible mantel meets the minimum height and width requirements for a combustible...

Страница 29: ...r over the front face of the fireplace NO PORTION OF GRILL AREA OR DOOR AREAS CAN BE COVERED except where designer clean view kit is used Combustible material can extend flush to unit up to the top bo...

Страница 30: ...set screw on the side of vari able speed controller to increase or decrease the minimum fan speed lowering minimum fan speed will decrease sound level created by fan Reinstall switch into wall mount a...

Страница 31: ...pronged grounding plug for your protection against shock hazard and should be plugged directly into a properly grounded three prong receptacle Label all wires prior to disconnection when servicing con...

Страница 32: ...Remove 2 DT Screws from Firebox sides Do not discard these screws Place Side Panels into Firebox as shown in Ref 3 below tilt and slide into place Replace and tighten DT Screw through hole in top of S...

Страница 33: ...ce optional front bridge ledge 3 in the area front of false bottom 5 Place rear Brick Panel 4 up against the rear of Firebox by tilting top of panel towards you and sliding bot tom of Panel over the b...

Страница 34: ...k Clip out of the way and slide Side Panel up against Back Panel Side Panel tabs should engage top and bottom of Back Panel See Ref 3 Rotate Brick Clip down over Side Panel and tighten screw 5 Re inst...

Страница 35: ...ng its individual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1 2 PSIG 3 5 KPa Note The gas line connection may be made of 1 2 rig...

Страница 36: ...ly the pilot burner located on the rear center left hand side of the main burner If a flame has appeared then continue to depress the control knob for 20 seconds If the flame did not appear then conti...

Страница 37: ...as valve Should read 325 millivolts minimum while holding valve knob depressed in pilot position and wall switch off Replace faulty generator if reading is below specified minimum Plugged burner orifi...

Страница 38: ...ing Burner System 1 Disconnect gas line connection at burner system through access cover opening CAUTION ALL WORK SHOULD BE PERFORMED BY A QUALI FIED AND CERTIFIED TECHNICIAN 2 Remove extension knobs...

Страница 39: ...intermittent or standing pilot system even if the main burner was never on Exercise caution when working within the area ALL WORK SHOULD BE PERFORMED BY A QUALIFIED AND CERTIFIED TECHNICIAN Monthly F...

Страница 40: ...ition of vent and vent terminal for sooting or obstruction and correct if present 6 Vacuum and clean any debris in the firebox that is not supposed to be there 7 Test and measure the flame failure res...

Страница 41: ...66 36 1000 P201VE Hex 3 16 1002 P013SI 907 013 4236RBT CKLP MQRB4236LPT Propane Conversion Millivolt 1001 P167SI 30 977 167 53 1000 P201VE Hex 1 4 1001 P201SI 0 907 201 4236RBT CKLPI MQRB4236LPTE Prop...

Страница 42: ...he correct setting as specified in the manual or label plate To adjust air setting loosen screw on the side of air mixing tube and rotate to the correct opening using a drill bit or tape measure Retig...

Страница 43: ...njector near the top Propane injectors have a groove machined around their circumference near the top while NG injectors do not have a groove fig 4 Refer to the Appliance Manufacturer s instruction sh...

Страница 44: ...Gas Conversion for Modulator PART C WARNING WARNING 44...

Страница 45: ...heat silicone tempera ture resistant to 500 F 260 C apply a con tinuous bead of approximately 1 32 to all four sides of frame and insert glass with new gas ket Frame should be on flat surface with a...

Страница 46: ...tom of logs 4 and 5 Position them onto left and right log placement tabs STEP 4 Locate the hole on the bottom of log 6 Place onto the mounting tab on log 2 Locate the 2 holes on the bottom of log 7 Pl...

Страница 47: ...Pilot Shield RSP1 RSP2 Qty 1 Shield Per Kit Back View 1 2 3 4 5 6 SLOTS SLOTS SLOTS SLOTS 47...

Страница 48: ...orts and the grate bar STEP 2 Attach the back rock support with the 4 screws as shown Replace reinstall the 2 screws from the grate bar STEP 3 Using the platform mount access holes attach the rock pla...

Страница 49: ...STEP 7 Place rocks 4 onto the burner as shown STEP 8 Place rocks 6 onto the burner as shown STEP 9 Place remaining rocks 4 and 6 into position as shown Finished Rock F2 Setup Placement of rocks for s...

Страница 50: ...tall the 2 screws from the grate bar STEP 2 Attach the back rock support using the existing screws from the back log holder Using the platform mount access holes attach the rock platform as shown STEP...

Страница 51: ...shown Do not place rocks directly onto the burner tubes STEP 6 Place rocks 4 into position as shown STEP 7 Place rocks 6 into position as shown STEP 8 Place remaining rocks 4 and 6 into position as sh...

Страница 52: ...nition can occur The following types of glass are approved Ember Glass Material from American Fireglass Maximum amount Natural Gas is 5 lbs Propane units 5 lbs Liquid Glass from Firegear Maximum amoun...

Страница 53: ...KIT Optional Accent Lighting Kit See separate installation page NOTE Glass Media must be evenly spread over the Burner and False Bottom as described on last page before Rock Stones and Log Accessorie...

Страница 54: ...t lamp wires through access hole in firebox as above Apply new sealant Mill Pac Secure Lamp Plate with screws Please follow the current ANSI NFPA 70 National Electrical Code in the USA and CAN CSA C22...

Страница 55: ...facing upward or sideways Replace burner tube and false bottom along with pilot shield STEP 4 Connect switch wires between lamp wire and transformer see schematic Connect remaining lamp wire to trans...

Страница 56: ...ppliance is still operable NOTE In certain instances the IPI Main Module requires resetting This can occur if the system is unable to ignite the pilot or the main burner in the allotted time period Th...

Страница 57: ...splay on the Transmitter will change to show that the room thermostat is ON and the set temperature is now displayed To adjust the set temperature press the Up or Down Arrow Keys until the desired set...

Страница 58: ...P 977 168 35 IPI 11 1002 P012SI IPI Stepper Kit LP 907 012 12 1002 P013SI IPI Stepper Kit NG 907 013 13 1002 P014SI IPI Reg Kit LP Hi Lo 907 014 14 1002 P016SI IPI Reg Kit NG Hi Lo 907 016 15 1002 P01...

Страница 59: ...Configuration 1 Basic manual HI LO and manual ON OFF capabilities 59...

Страница 60: ...Receiver Module 584 523 521 221 1001 P221SI Receiver Module 584 523 521 221 1001 P221SI 60...

Страница 61: ...er Adapter P N 1002 P850si The Remote Receiver IPI or Millivolt system can be powered by the AC Adapter This is advantageous if you do not want to use batteries Simply connect the AC Adapter into the...

Страница 62: ...Configuration 3 Remote ON OFF variable HI LO and fan capabilities Refer to the fan installation removal section for fan installation 62...

Страница 63: ...clockwise to off Located behind the access panel 7 Wait five 5 minutes to clear out any gas Then smell for gas including near the floor If you smell gas STOP Follow B in the safety information above...

Страница 64: ...IPI Assembled NG 199 033 14 1002 P047SI TC Pilot Burner IPI Assembled LP 199 047 15 1001 P166SI TC Orifice Pilot NG 977 166 62 IPI 16 1001 P168SI TC Orifice Pilot LP 977 168 35 IPI 17 1001 P280SI TC T...

Страница 65: ...must be followed to reset the PF2 Module Press the Red SW1 button until you hear three beeps Within 10 seconds press the SW1 button again until you hear it beep The PF2 Module may now be turned on off...

Страница 66: ...ON OFF and the pilot is also out follow the procedures described in this manual to light the pilot To switch from IPI to CPI Mode 1 Turn the fireplace OFF using the ON OFF Key 2 Press the Mode Key Dis...

Страница 67: ...Proflame 2 Remote Control 67...

Страница 68: ...Note When Smart Thermostat is activated manual flame height adjustment is disabled Note This function is only available in Room Thermostat or Smart Thermostat Control Mode 68...

Страница 69: ...69...

Страница 70: ...3 m horizontally L Clearance above paved sidewalk or paved driveway located on public property 7 ft 2 13 m Notes 2 M Clearance under veranda porch deck or balcony 12 in 30 cm 12 in 30 cm N Where a ve...

Страница 71: ...ends place spring in bend or before and after See Fig 1 Horizontal runs require support metal straps every 2 feet In offset installation support straps should be used to stabilize pipe Expand 4 and 7...

Страница 72: ...the 4 flex pipe as required Then attach the seven inch 7 pipe by the same method 8 Support horizontal pipes every two 2 feet 61 cm with metal strap bands Re check fireplace to make sure it is levelle...

Страница 73: ...and the number of bends required 2 Having determined the vertical distance determine the maxi mum horizontal section allowed 3 Vent table has been established for 90 horizontal vertical runs With use...

Страница 74: ...w well is recommended with adequate and proper drainage as per local codes Leave 2 clearance below snorkel to prevent water from entering the Snorkel Termination Do not enclose the Snorkel within a wa...

Страница 75: ...rulers or by using a roof pitch card Slide a Roof Flashing suitable to your roof slope over the vent Place the edge of the flashing plate that will be on the higher part of the roof slope under the sh...

Страница 76: ...upport configuration B Flex bend configuration C Termination mounting Clearance to perpendicular wall 24 inches 60 cm Recommended to prevent re circulation of exhaust products For additional requireme...

Страница 77: ...eep toddlers young children and other at risk individuals out of the room and away from hot surfaces Do not leave the fireplace remote control where it is accessible to children Termination Cap Safety...

Страница 78: ...s are permitted however Cold Climate Switch Standing Pilot Mode must NOT be used Seven 90 elbows are possible if the total horizontal is not more than 25ft and the vertical does not exceed 15ft Refer...

Страница 79: ...not supplied to connect to the Power Vent Termination SECTION 2 FLEX VENT Used for entire installation order Z47PVA Note Must use a one foot section of 5 8 DV hard pipe connected to the power vent on...

Страница 80: ...OWER VENT ACCESSORIES ZDV4FC Flex Connector 4 Diameter ZDV7FC Flex Connector 7 Diameter ZDV4FCL Flex Clamp 4 ZDV7FCL Flex Clamp 7 ZDV4SS Spring 4 Standoff Spacer PVH58WT Wall Thimble for Power Vent 80...

Страница 81: ...hemicals other than in a normal residential environment c damages caused by any unauthorized alteration or repair of the unit affecting its stability or performance d damages caused by improper matchi...

Отзывы: