96
User’s Manual
PMX_MULTI
Appendix
Factory Default Settings
If you hold down LOCAL and LOCK and turn the POWER switch on, the product will be initialized to its fac-
tory default settings.
The voltmeter displays “
INIT
,” and the product is set to factory default settings.
Basic settings
CONFIG settings
Basic item
Description
Output voltage
0 V
Output current
Maximum settable current
OVP (overvoltage protection)
110 % of the rated output voltage
OCP (overcurrent protection)
110 % of the rated output current
Memory values A, B, C
Output voltage, output current, OVP, OCP: Factory default settings
output-on delay/ off delay time: 0.0 s
Parameter
number
Setting/ display
Description
CF01
Output state at power-on
SAFE (output off)
CF02
Memory content display
ON (displayed)
CF03
Key lock content
LOC3 (Lock all keys and the rotary knob)
CF04
*1
*1.
Can be set separately for each channel
External control for turning output on/off
OFF (not controlled)
CF05
*1
External control logic for turning output on/off LO (a LOW signal turns output on)
CF06
*1
Output-on startup state
CV (CV is prioritized)
CF07
*1
Rise time when a value is changed
SLOW (the output voltage rises in 100 ms)
CF08
Output state when a protection function
(OVP/OCP) is activated
ALL (all channels off)
CF09
*1
Tracking operation
CH1 on, CH2 on
CF20
LAN interface
ON (use)
CF21
USB interface
ON (use)
CF22
RS232C interface
ON (use)
CF23
SCPI communication error display
OFF (not displayed)
CF24
Communication monitoring (watchdog) timer OFF (timer off)
CF25
Buzzer on/off
ON (Buzzer on)
CF40
LAN setting reset (LCI/DEF)/apply (APPL)
LCI (LAN interface setting reset)
CF41
IP address assignment method
110 (DHCP on, AUTO IP on, MANUAL IP off)
CF46
IP address subnet mask
24
CF51
RS232C baud rate
19.2 (kbps)