PFX2512
77
PFX2512 Functional Specifications
5
Specific
a
tions
Other functions
Interface
Range switching
Voltage range
6 V
-1.0000 to 6.0000
The display resolution is 100 μV.
60 V
-6.0000 to 60.0000
Pattern charge/discharge function
(seamless charge/discharge control)
1
1.
Can control DC power supplies and electronic loads at the same time in order to seamlessly switch between
charge and discharge.
Response within 50 ms (TYP)
2
2.
Indicates the current response speed when the waveform changes from charging to discharging and
discharging to charging at the rated current.
It is defined as the time for the charge/discharge current to change from 10 % to 90 % of the preset value
(rated value).
DC power
supply I/F
Kikusui’s dedicated DC power
supply connector
1
1.
Can be connected directly to PWRs and PASs, can be connected to the PWR-01 using the SC07-PFX I/F cable
(option)
1 channel, 26-pin connector, isolation I/O
Electronic load
I/F
Kikusui’s dedicated electronic
load connector
2
2.
Can be connected directly to PLZ-4Ws, can be connected to the PLZ-5W using the SC05-PFX I/F cable (option)
1 channel, 20-pin connector, isolation I/O
System
communicatio
n
LAN (Ethernet)
1 channel; use BPChecker3000
10Base-T/100Base-TX
3
RJ45 connector (Can be a straight cable or a crossover cable)
3.
The IP address is assigned automatically through DHCP or set manually through IO Config.
External
control
REST status signal output
Low level when resting; isolated open collector output
4
4.
Withstand voltage is 80 Vdc against other circuits. Application voltage 30 Vmax, sink current 8 mAmax
END status signal output
Low level when a test finishes; isolated open collector output
4
ALM status signal output
Low level in alarm state; isolated open collector output
4
CHG status signal output
Low level when charging; isolated open collector output
4
DISCHG status signal output
Low level when discharging; isolated open collector output
4
External alarm input
Low level to abort testing. Pulled up to +5 V by 5.1 kΩ.
Expansion slots
3 slots for optional boards
Содержание PFX2500 Series
Страница 12: ...12 PFX2512 This page is intentionally blank ...
Страница 27: ...Connecting and Configuring Devices This chapter describes how to connect and configure the devices ...
Страница 62: ...62 PFX2512 This page is intentionally blank ...
Страница 71: ...Specifications This chapter provides the PFX2512 s specifications and outline drawing ...
Страница 96: ...96 PFX2512 This page is intentionally blank ...
Страница 140: ...140 PFX2512 Troubleshooting This page is intentionally blank ...
Страница 143: ......